FieldSmart
®
Fiber Active Cabinet (FAC) 400
Installation Manual
_________________________________________________________
Proprietary Information: Not for use or disclosure except by written agreement with Clearfield.
86
Installing the Rectifier Modules (Alpha Cordex Rectifier Option)
The FAC 400 Rectifier shelf uses the 19-inch Alpha Cordex HP 1.2kW 1RU rectifier shelf to generate and distribute -48
VDC bulk power.
The Alpha shelf supports up to two rectifier modules. Normal operation for the FAC 400 Power Hub requires two 25A
rectifier modules.
Install Alpha rectifier modules into the shelf as described below.
Note:
The controller module ships installed in the rectifier shelf. Push firmly on the controller module to verify that it is fully
seated in the slot.
CXCM1+Controller
48v 1.2kW Rectifier Module
Note:
The far right slot does not support a rectifier module.
The Alpha shelf provides integrated distribution, with 8 GMT fuse positions for equipment. The Alpha shelf is equipped
with a Cordex CXCM1+ controller module that monitors power functions and alarm information and regulates voltage in
response to battery temperature. The controller module ships pre-programmed for operation in the FAC 400 Power Hub.
For a complete description of the controller module, refer to the Cordex Controller Software Manual.