Install the protective covers (manufacturer-supplied) over each battery terminal, and then slide the battery
string into the riser compartment battery tray.
In the upper battery compartment, do the following:
a.
Remove the front retainer bracket from the battery tray.
Note:
If you are using the optional battery heater, install the heater before installing batteries. See Installing a
Battery Heater for instructions.
b.
Locate the secondary battery supply leads and the (installed) main secondary battery string.
The battery supply leads ship in a bag.
c.
Connect the Anderson connector on the battery supply leads to the Anderson connector on the main
secondary battery string.
d.
Route the battery supply leads along the sides of the battery tray and then arrange a string of four batteries
with the terminals accessible in front.
Note:
You will slide the batteries into the battery tray after installing the cables and protective covers.
Step 9: