111
FieldSmart
®
Fiber Active Cabinet (FAC) 900
__________________________________________________________
Installation Manual
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeClearfield.com • techsupport@clfd.net
Manual 020420 REV B - April 2019
Step 3:
Changing the alarm setting:
a.
Navigate to
Alarms > Configure Alarms.
b.
In the Alarm Configuration drop down box, select Voltage Alarms.
c.
Enter the High Voltage 1 and High Voltage 2 in the Activation Value box.
Alarm Name
Activation Value
High Voltage 1
56.5
High Voltage 2
56.6
Rectifier Setting Name
Value
Float Voltage
54.48
Equalize Voltage
56.3
OVP
57.7
LVA
46.0
HVA
56.5
d.
Navigate to
Rectifiers > Configure Rectifiers
.
e.
Enter the following in its respective box.