Cleaning an MPO/MTP Connector
Female Connector
• Place one wiping paper on QbE-2 FiberSafe™ Cleaning Platen and
apply small amount of precision cleaner (about 1” in diameter) with
Electro-Wash MX pen on to one end of the wipe. (
Figure 1)
Figure 1
Figure 2
Figure 3
•
Hold end face at a 90 degree angle. For APC connection, adjust by
slightly tilting the container or end face. Angle is correct when no drag is
felt on the end face. (
Figure 2)
Male Connector
•
Lightly moisten one side of the fiber optic swab (CC505F) by spotting a
small amount (about 1”) of Electro-Wash PX or Electro-Wash MX pen
onto the QbE. Hold the swab, 1 side down to the wetted area and hold
for a count of 1-2-3-4-5.
• Place swab, wet side down, at one end of connector end face and draw
across in a diagonal sweep; i.e., from fiber 1 up and across to fiber 12.
Turn swab over to dry and draw back from fiber 12 to fiber 1. (
Figure 3)