Standard Economizers
Part No. 750-266
1-
11
1.7.2 - Stack Corrosion Control
Stack Corrosion Control holds the stack temperature down in order to prevent condensation and
corrosion. The damper will automatically modulate to maintain a predetermined temperature.
ELECTRICAL COMPONENTS
1. INDICATING CONTROL PANEL (combining Automatic Sootblower and Stack Corrosion Control)
including:
• Terminal Strip providing customer 120V power connection and a thermocouple connection.
• “Power on/off” switch and “Indicating light” opens the circuit to operate the Stack Corrosion Control
Assemblyincluding the indicating controller modulating damper actuator, and thermocouple.
• “Sootblower on/off” switch opens the circuit to operate the Timed Automatic Sootblower Assembly
including the Electric Steam Valve Assembly, Pneumatic Drive Cylinder Assembly.
• Duration Timercontrols the length of time between sootblowing cycles (off/interval) and the length of time
at the Pneumatic Drive Cylinder Assy. (on/duration). A control knob for each setting allows for specific
times within the ranges.
• Delay Timer controls the Electric Steam Valve Assembly and the Modulating Electric Valve Assembly
duringthe sootblowing cycle causing the controller to put the Damper Actuator in an override position,
driving thedamper(s) to the bypass position. When the Pneumatic Cylinder Assembly returns to its original
position,the delay timer causes the Steam Valve to close and returns the Thermocouple to its normal
function concerning the Stack Corrosion Control.
2. PNEUMATIC DRIVE CYLINDER ASSY is controlled by a solenoid valve. The solenoid is energized at
the beginning ofthe sootblowing cycle by the Delay Timer, allowing the ram to move outward to its
furthest position. At the end of its stroke the timer de-energizes the solenoid valve, allowing the
stroke to retract to its original position.
3. MODULATING ELECTRIC DAMPER ASSY receives a signal from the temperature controller and mod-
ulates the dampersto bypass the flow of exhaust, to maintain the desired temperature. During the
sootblowing cycle damper moves to the full bypass position. This allows the soot to be blown out
through the center of the economizer until the end of the sootblowing cycle.
4. ELECTRIC STEAM VALVE ASSY is energized to open (5 seconds) during sootblowing operation allow-
ing 50-100 PSIG steam to the sootblower assembly - and energized again to close after the soot-
blowing cycle is complete.
5. EXHAUST TEMPERATURE INDICATING CONTROLLER(for Stack Corrosion Control) receives a signal
from thethermocouple sensing the exhaust temperature leaving the economizer and controls the
Modulating Electric Damper Assembly.
6. THERMOCOUPLE (for Stack Corrosion Control) is remote mounted (by others) sensing the exhaust
gas temperature leaving the economizer.
FUNCTION
Timed Automatic Sootblower design is a fully adjustable sootblower which avoids day-to-day opera-
tor attendance by running the sootblower in specific timed intervals. The actual blowing down of
soot collecting on the fins utilizes special flood-jet type nozzles for achieving maximum velocity and a
concentrated spray pattern specifically directed at the heat transfer surfaces. The Sootblower
Assembly contains ring nozzle assembly(s) for inward blowing per standard economizer, with a varied
Summary of Contents for C1X Series
Page 1: ...Economizers 750 266 1 15 CRE CCE C2X C1X Operation Manual...
Page 2: ......
Page 6: ...vi NOTES...
Page 20: ...Standard Economizers 1 14 Part No 750 266 Figure 1 7 Piping with circulating tank BOILER...
Page 29: ...Condensing Economizers Part No 750 266 2 9 Figure 2 7 Dimension diagram C2X BB...
Page 33: ...Condensing Economizers Part No 750 266 2 13 Figure 2 9 Single boiler with deaerator...
Page 39: ...Condensing Economizers Part No 750 266 2 19 Figure 2 11 Two boilers with deaerator...
Page 51: ...Condensing Economizers Part No 750 266 2 31...
Page 52: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...