Standard Economizers

Part No. 750-266

1-

11

1.7.2 - Stack Corrosion Control

Stack Corrosion Control holds the stack temperature down in order to prevent condensation and
corrosion. The damper will automatically modulate to maintain a predetermined temperature.

ELECTRICAL COMPONENTS

1. INDICATING CONTROL PANEL (combining Automatic Sootblower and Stack Corrosion Control) 

including:

•  Terminal Strip providing customer 120V power connection and a thermocouple connection.

•  “Power on/off” switch and “Indicating light” opens the circuit to operate the Stack Corrosion Control 

Assemblyincluding the indicating controller modulating damper actuator, and thermocouple.

•  “Sootblower on/off” switch opens the circuit to operate the Timed Automatic Sootblower Assembly 

including the Electric Steam Valve Assembly, Pneumatic Drive Cylinder Assembly.

•  Duration Timercontrols the length of time between sootblowing cycles (off/interval) and the length of time 

at the Pneumatic Drive Cylinder Assy. (on/duration).  A control knob for each setting allows for specific 
times within the ranges. 

•  Delay Timer controls the Electric Steam Valve Assembly and the Modulating Electric Valve Assembly 

duringthe sootblowing cycle causing the controller to put the Damper Actuator in an override position, 
driving thedamper(s) to the bypass position. When the Pneumatic Cylinder Assembly returns to its original 
position,the delay timer causes the Steam Valve to close and returns the Thermocouple to its normal 
function concerning the Stack Corrosion Control.

2. PNEUMATIC DRIVE CYLINDER ASSY is controlled by a solenoid valve.  The solenoid is energized at 

the beginning ofthe sootblowing cycle by the Delay Timer, allowing the ram to move outward to its 
furthest position.  At the end of its stroke the timer de-energizes the solenoid valve, allowing the 
stroke to retract to its original position. 

3. MODULATING ELECTRIC DAMPER ASSY receives a signal from the temperature controller and mod-

ulates the dampersto bypass the flow of exhaust, to maintain the desired temperature.  During the 
sootblowing cycle damper moves to the full bypass position.  This allows the soot to be blown out 
through the center of the economizer until the end of the sootblowing cycle. 

4. ELECTRIC STEAM VALVE ASSY is energized to open (5 seconds) during sootblowing operation allow-

ing 50-100 PSIG steam to the sootblower assembly - and energized again to close after the soot-
blowing cycle is complete.

5. EXHAUST TEMPERATURE INDICATING CONTROLLER(for Stack Corrosion Control) receives a signal 

from thethermocouple sensing the exhaust temperature leaving the economizer and controls the 
Modulating Electric Damper Assembly.

6. THERMOCOUPLE (for Stack Corrosion Control) is remote mounted (by others) sensing the exhaust 

gas temperature leaving the economizer.

FUNCTION

Timed Automatic Sootblower design is a fully adjustable sootblower which avoids day-to-day opera-
tor attendance by running the sootblower in specific timed intervals.  The actual blowing down of 
soot collecting on the fins utilizes special flood-jet type nozzles for achieving maximum velocity and a 
concentrated spray pattern specifically directed at the heat transfer surfaces.  The Sootblower 
Assembly contains ring nozzle assembly(s) for inward blowing per standard economizer, with a varied 

Summary of Contents for C1X Series

Page 1: ...Economizers 750 266 1 15 CRE CCE C2X C1X Operation Manual...

Page 2: ......

Page 3: ...chase orders for replacement manuals to your local Cleaver Brooks authorized representative Manual Part No 750 266 1 15 Printed in U S A Cleaver Brooks 2015 CLEAVER BROOKS Economizers CRE CCE C2X C1X...

Page 4: ...how a basic burner operates Operating controls will normally function for long periods of time and we have found that some operators become lax in their daily or monthly testing assuming that normal...

Page 5: ...LATION 1 2 STARTUP 1 7 MONITORING PERFORMANCE 1 8 MAINTENANCE 1 8 OPTIONS 1 10 Section 2 Condensing Economizers C2X and C1X 2 1 GENERAL 2 2 UNLOADING 2 2 INSTALLATION 2 3 OPERATING SEQUENCES EXAMPLE I...

Page 6: ...vi NOTES...

Page 7: ...www cleaverbrooks com Section 1 Model CRE and CCE Economizers GENERAL 1 2 UNLOADING 1 2 INSTALLATION 1 2 STARTUP 1 7 MONITORING PERFORMANCE 1 8 MAINTENANCE 1 8 OPTIONS 1 10...

Page 8: ...ely to the carrier within the allowable time limit The CCE product line units are shipped in enclosed crates To remove the economizer first position the unit while either still in the shipping contain...

Page 9: ...uately supported In some cases the economizer may be placed directly on top of the combustion source in effect forming the first section of the exhaust duct with the existing exhaust stack lifted or c...

Page 10: ...he exchanger can then be set on the beams and slid to the lower stack and or stack adapter for final securing Position four 4 tie rods as specified and supplied by others which can be used to suspend...

Page 11: ...ent Drain piping should include valves of dependable manufacture in order to further reduce the possibility of an undetected leak Safety relief valves as required should be located at the exchanger an...

Page 12: ...oid safety valve leakage ensure that safety valve set pressure is sufficiently higher than dead head pressure of the feed pump It is recommended that the pipe and circulating tank if included be insul...

Page 13: ...of the system and begins to take on feedwater normal operation can resume If the final exhaust temperatures are too low pressure drop across the economizer is too high or if the desired water temperat...

Page 14: ...system containing a pump and BTU storage tank if the economizer pressure relief valve discharges it is likely that there is no or little liquid circulating through the economizer Check the pump opera...

Page 15: ...e initiated If the economizer is not equipped with a timed automatic sootblower the access door should be opened for inspection and cleaning A large access door optional hinged assembly available for...

Page 16: ...the flue gas stream The internal bypass damper must be in the open position during blowdown A routine blowdown schedule should be established at time intervals consistent with the soot loading charac...

Page 17: ...ASSY is controlled by a solenoid valve The solenoid is energized at the beginning ofthe sootblowing cycle by the Delay Timer allowing the ram to move outward to its furthest position At the end of its...

Page 18: ...r control of thesootblowing cycle as required A manual push button start located at the Pneumatic Drive Cylin der s solenoid allows for amanual override and is used to check test runs for speed at whi...

Page 19: ...xhaust outlet of the economizer begins to drop to a safe operating exit temperature the flow control valve is adjusted to maintain the proper flow required to stabilize the minimum desired gas tempera...

Page 20: ...Standard Economizers 1 14 Part No 750 266 Figure 1 7 Piping with circulating tank BOILER...

Page 21: ...s com Section 2 Model C2X and C1X Condensing Economizers GENERAL 2 2 UNLOADING 2 2 INSTALLATION 2 3 OPERATING SEQUENCES EXAMPLE INSTALLATIONS 2 12 ECONOMIZER CONTROLS 2 24 MONITORING PERFORMANCE 2 29...

Page 22: ...or further heating of the feedwater after it leaves the deaerator The C1X or the C2X upper stage can also be used to heat any other liquid besides boiler feedwater By matching the economizer with the...

Page 23: ...Cleaver Brooks representative for suggestions All exchangers include steel pads for mounting to the final support supplied by others as required by the installation NOTE Spare parts may be shipped wit...

Page 24: ...n no case should the static load on the economizer inlet or outlet flange exceed 500 pounds In no case should any moment be applied to the economizer inlet or outlet Four 4 lifting lugs are supplied o...

Page 25: ...tion to ensure that no outside forces from thermal expansion to either the exhaust gas connections or to the piping will be permitted Exhaust connections are generally mated with optional mating flang...

Page 26: ...floor support Figure 2 5 Installation horizontal flow unit w ceiling support Liquid connections are connected either with NPT threaded fittings or flange connections Liquid piping should include shut...

Page 27: ...ecommended in order to purge air out especially during initial start up 2 3 1 Special Installation Considerations The C B economizer may be installed inside or outside with appropriate drain piping in...

Page 28: ...lace Consult the factory for suitable descaling solutions 2 3 2 Condensing economizer dimensions and weights Table 2 1 Economizer weights C2X lbs Table 2 2 Dimensions C2X see Figure 2 7 all dimensions...

Page 29: ...Condensing Economizers Part No 750 266 2 9 Figure 2 7 Dimension diagram C2X BB...

Page 30: ...L286AL C1X R2D6AL C1X S2F6AL C1X Z2N6AL A 52 2 54 4 61 5 101 6 B 48 0 48 0 58 0 90 0 C 28 4 28 3 32 7 51 4 D 24 6 24 6 28 9 46 7 E 17 1 31 5 39 5 F 16 12 24 12 24 12 31 5 G 53 6 71 6 81 6 118 6 H 10 0...

Page 31: ...Condensing Economizers Part No 750 266 2 11 Figure 2 8 Dimension diagram C1X G K H J I L M N O A C B D E F I D AA BB...

Page 32: ...tion describes four typical configurations utilizing the C2X 2 stage economizer NOTE the examples given are for illustrative purposes only individual applications may vary Contact CB to determine the...

Page 33: ...Condensing Economizers Part No 750 266 2 13 Figure 2 9 Single boiler with deaerator...

Page 34: ...Condensing Economizers 2 14 Part No 750 266 NOTES to Figure 2 9 CONTACT LOCAL CB REPRESENTATIVE IZING...

Page 35: ...Condensing Economizers Part No 750 266 2 15 2 4 2 Single boiler with deaerator and surge tank refer to Figure 2 10...

Page 36: ...Condensing Economizers 2 16 Part No 750 266 Figure 2 10 Single boiler with deaerator and surge tank...

Page 37: ...Condensing Economizers Part No 750 266 2 17 NOTES to Figure 2 10 CONTACT LOCAL CB REPRESENTATIVE IZING SURGE TANK...

Page 38: ...Condensing Economizers 2 18 Part No 750 266 2 4 3 Two boilers with deaerator refer to Figure 2 11...

Page 39: ...Condensing Economizers Part No 750 266 2 19 Figure 2 11 Two boilers with deaerator...

Page 40: ...Condensing Economizers 2 20 Part No 750 266 NOTES to Figure 2 11 CONTACT LOCAL CB REPRESENTATIVE IZING...

Page 41: ...Condensing Economizers Part No 750 266 2 21 2 4 4 Two boilers with deaerator and surge tank refer to Figure 2 12...

Page 42: ...Condensing Economizers 2 22 Part No 750 266 Figure 2 12 Two boilers with deaerator and surge tank...

Page 43: ...Condensing Economizers Part No 750 266 2 23 NOTES to Figure 2 12 CONTACT LOCAL CB REPRESENTATIVE IZING SURGE TANK...

Page 44: ...ystem features 5 7 color touchscreen display Digital inputs for fuel type selection Relay outputs for valve control and remote alarm indication Analog inputs for economizer water temperature flue gas...

Page 45: ...raphical overview screen displays an overview of economizer performance The setpoint entry screens allow the user to configure the system to match individual project requirements These screens are pas...

Page 46: ...y screen informs the operator of any operating conditions that fall outside of the norm The analog configuration screens allows the user to easily set the scaling values for the analog I O These scree...

Page 47: ...uthorized access 2 5 2 CEC 10x System features 128x64 monochrome LCD display with push button style operator interface Digital inputs for fuel type selection Relay outputs for valve control and remote...

Page 48: ...allows the user to configure the system to match individual project requirements This screen is password protected to discourage unauthorized access The digital I O screens allow the user to manually...

Page 49: ...from the 2 oil from combining with condensate and forming sulfuric acid which would destroy the metallic components In near condensing mode any cold makeup water is routed to the dearator and not thro...

Page 50: ...er core area will depend on the conditions of temperature and the quality of combustion within the flue gas stream NOTE Ensure that the combustion source is off and is cool and that the economizer is...

Page 51: ...Condensing Economizers Part No 750 266 2 31...

Page 52: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...

Reviews: