Condensing Economizers
Part No. 750-266
2-5
Structural integrity of the building should be verified (by others) prior to installing an economizer by
suspending from the ceiling.
Apply expansion joints (supplied by others) as required by the installation to ensure that no outside
forces from thermal expansion to either the exhaust gas connections or to the piping will be permitted.
Exhaust connections are generally mated with optional mating flanges and/or stack transitions. The
mating flanges can be butt or slip fit welded to the stack breaching once aligned. Ensure that the
economizer is level before final welding and/or bolting into position.
Figure 2.3 - Installation, vertical flow units