Chapter 5 — Starting and Operating Instructions
Part No. 750-184
5-15
adjustment of the burner over the entire firing range. When a
shutdown occurs while operating in the manual position at other
than low fire, the damper will not be in a closed position, thus
allowing more air than desired to flow through the boiler. The
cycling of hot flame to cool air subjects the pressure vessel metal
and refractory to undesirable conditions.
With the switch set at “auto,” the burner will operate on a
modulating basis according to the load demand.
The burner will continue to operate with modulated firing until the
operating limit pressure or temperature is reached, unless:
1. The burner is manually turned “off.”
2. A low-water condition is detected by low-water level control.
3. The electrical or fuel supply is interrupted.
4. The combustion air pressure or atomizing air pressure drops
below minimum level.
Note: There can be other reasons for shutdown such as motor
overload, flame outages, tripped circuit breakers, blown
fuses, or through other interlock devices in the circuitry.
When the burner is shut down normally, by either the
Operating
Limit Control
or by manually switching the burner off, the load
demand light no longer glows.
Shutdown through conditions causing safety or interlock controls to
open will actuate the
Flame Failure Light
(and alarm if so equipped)
and the
Load Demand Light
will remain lit. The cause of this type
of shutdown will have to be located, investigated, and corrected
before operation can be resumed. Refer to the “trouble-shooting”
section in Chapter 7.
Shutdown
- When the
Operating Limit Control
setting is reached to
open the circuit or if the burner switch is turned “off,” the following
sequence occurs.
The fuel valve is deenergized and the flame is extinguished. The
timer begins operation and the blower motor continues running to
force air through the furnace in the post-purge period.
At the end of the programmed post-purge period, the blower motor
is turned off. The air pump motor of an oil-fired burner is also turned
off. The timer has returned to its original starting position and stops.
The unit is ready to re-start.
!
Warning
It is advisable to check for tight shut-off of fuel valves. Despite
precautions and strainers, foreign material in either new or
renovated fuel lines may lodge under a valve seat and prevent tight
closure. The situation is especially true in new installations.
Promptly correct any conditions causing leakage. Failure to follow
these instructions could result in serious personal injury or death.
Summary of Contents for CB Ohio Special 100 HP
Page 2: ...ii ...
Page 8: ...viii ...
Page 42: ...Chapter 2 Burner Operation and Control 2 22 Part No 750 184 ...
Page 116: ...Chapter 6 Adjustment Procedures 6 28 Part No 750 184 ...
Page 126: ...Chapter 8 Inspection and Maintenance 8 6 Part No 750 184 ...
Page 153: ...Chapter 9 Parts Part No 750 184 9 3 Insulated Front Head Model CB LE ...
Page 154: ...Chapter 9 Parts 9 4 Part No 750 184 Insulated Front Head Interior Model CB LE ...
Page 155: ...Chapter 9 Parts Part No 750 184 9 5 Insulated Inner Door Model CB OS ...
Page 156: ...Chapter 9 Parts 9 6 Part No 750 184 Insulated Rear Head CB LE ...
Page 157: ...Chapter 9 Parts Part No 750 184 9 7 Insulated Rear Head CB LE ...
Page 158: ...Chapter 9 Parts 9 8 Part No 750 184 Insulated Rear Head CB OS ...
Page 159: ...Chapter 9 Parts Part No 750 184 9 9 Dry Oven Model CB LE ...
Page 161: ...Chapter 9 Parts Part No 750 184 9 11 Motor Impeller Model CB LE ...
Page 162: ...Chapter 9 Parts 9 12 Part No 750 184 Front Head Linkage ...
Page 170: ...Chapter 9 Parts 9 20 Part No 750 184 Control Cabinet Hawk ICS ...
Page 171: ...Chapter 9 Parts Part No 750 184 9 21 Control Panel Standard ...
Page 172: ...Chapter 9 Parts 9 22 Part No 750 184 Entrance Box ...
Page 173: ...Chapter 9 Parts Part No 750 184 9 23 Front Head Electrical CB LE ...
Page 174: ...Chapter 9 Parts 9 24 Part No 750 184 Front Head Electrical CB LE ...
Page 175: ...Chapter 9 Parts Part No 750 184 9 25 Front Head Electrical CB OS ...
Page 176: ...Chapter 9 Parts 9 26 Part No 750 184 Front Head Electrical CB OS ...
Page 179: ...Chapter 9 Parts Part No 750 184 9 29 Heavy Oil Piping 60 Steam CB LE ...
Page 180: ...Chapter 9 Parts 9 30 Part No 750 184 Heavy Oil Piping 60 Steam CB LE SEE TABLE NEXT PAGE ...
Page 181: ...Chapter 9 Parts Part No 750 184 9 31 Common Oil Parts Heavy Oil ...
Page 182: ...Chapter 9 Parts 9 32 Part No 750 184 Side Mounted Air Compressor Piping ...
Page 183: ...Chapter 9 Parts Part No 750 184 9 33 Air Compressor Piping CB OS ...
Page 185: ...Chapter 9 Parts Part No 750 184 9 35 Light Oil Piping ...
Page 186: ...Chapter 9 Parts 9 36 Part No 750 184 Light Oil Air Piping Front Head ...
Page 187: ...Chapter 9 Parts Part No 750 184 9 37 Light Oil Air Piping Front Head PAGE 9 31 ...
Page 191: ...Chapter 9 Parts Part No 750 184 9 41 Gas Train 125 150 HP ...
Page 193: ...Chapter 9 Parts Part No 750 184 9 43 Gas Train 200 HP ...
Page 195: ...Chapter 9 Parts Part No 750 184 9 45 Steam Pressure Controls ...
Page 196: ...Chapter 9 Parts 9 46 Part No 750 184 Hot Water Temperature Controls ...
Page 197: ...Chapter 9 Parts Part No 750 184 9 47 Water Column ...
Page 198: ...Chapter 9 Parts 9 48 Part No 750 184 Water Column ...
Page 199: ...Chapter 9 Parts Part No 750 184 9 49 Fireside Gaskets CB LE ...
Page 200: ...Chapter 9 Parts 9 50 Part No 750 184 Fireside Gaskets CB OS ...