background image

1948881 

V1.4 

12 August 2022 

 

Clevertest and Clevertest Plus 

 

Refer to the supplementary operation guide supplied with the Product. 

 

Zoneworks, HIVE and DATA Monitored Options

 

Fittings  with  part  numbers  -ZW

,  -HV/-HVG,  -DATA 

are  fitted  with  Zoneworks  communications  modules 

(nodes).  These  fittings  are  monitored  using  either  Powerline  Carrier  Technology  that  utilize  the  power 
cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated 
data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can also 
be  connected  via  Ethernet/Internet/Fibre).  Zoneworks  software  on  the  server  is  used  to  monitor, 
coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by a 
single push of the test switch or by scanning the supplied barcode. The LED Test Switch indicator provides 
a multifunction indication of the status of the fitting during testing and normal operation: 

Option 

State 

LED Operation 

ZW, HV, HVG, DATA 

Commissioned 

LED on Solid (Green) 

ZW, DATA 

Un-commissioned 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HV, HVG 

Un-commissioned 
With network connectivity 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HV, HVG 

Un-commissioned 
Without network connectivity 

Batt plugged-in:

 yellow 250mS, 

green 250mS, yellow 250mS, green 
250mS, green 1s 

Batt unplugged:

 red 250mS, off 

250mS, red 250mS,off 250mS, off 1s 

ZW, DATA 

Emergency Light Test In Progress 

LED flashes at yellow 5s , 0ff 1s 

HV, HVG 

Emergency Light Test In Progress 

LED flashes at yellow 1s , 0ff 1s 

In the case of the DATA version a 2-

way “figure 8” cable and terminal block facilitates the connection to 

the DATA network via a multi-drop bus (daisy chain connection).  For further information of installation of 
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA 
version)  

DALI EM Option

 

Luminaires with part numbers having 

-DALI 

are fitted with DALI modules (nodes) that facilitate connection 

and integration to 3

rd

 Party Lighting Control Systems.  Before installing the -DALI luminaire, please confirm 

that the Lighting Control System has the capability to monitor DALI Emergency Luminaires.  The  -DALI 
fitting  will  be  addressed  and  configured  into  the  control  system  by  the  Lighting  Control  System 
Commissioning Technicians and not Clevertronics.   

State

 

LED Operation

 

Commissioned/ Un-commissioned 

LED on Solid (Green) 

Emergency Light Test in progress 

LED flashes at 1s On (Yellow) & 1s Off 

“IDENTIFY COMMAND” 

Lamp and Status LED Flash for 30 seconds 

 
A 2-

way “figure 8” cable and terminal block facilitates the connection to the DALI network.  DALI 

connections are marked as Da Da.  

Rated Emergency Lumen Output in accordance with AS2293.1 (refer to 
spacing tables for installation positions): 

Refer to the Technical Label for classification information. 

Caution: 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life 
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 
abuse, are specifically EXCLUDED from Clevertronics warranty terms. 

 

 

Argonaut PRO Weatherproof Emergency LED Batten 

Installation & Maintenance Instruction Leaflet

 

 

 

Victoria (Head Office & Manufacturing) 

Website:

 

www.clevertronics.com.au

 

Email:

 

info@clevertronics.com.au

 

Phone:

 +61 3 9559 2700  

Fax:

 +61 3 9559 2799 

New South Wales

 

Phone:

 +61 2 8805 6400 

Fax:

 +61 2 8805 6444

 

Queensland

  

Phone:

 +61 7 3442 9700 

Fax:

 +61 7 3442 9777 

 

South Australia/Northern Territory

  

Phone:

 +61 8 8301 8800 

Fax:

 +61 8 8351 8286 

 

Western Australia

  

Phone:

 +61 8 9207 0000 

Fax:

 +61 8 9207 0088 

 

New Zealand 

Phone:

 +64 800 548 448 

Designed in Australia to comply with the requirements 
of AS/NZS2293.3: 2018, AS CISPR 15: 2017

 

 

Models:  

 

ARGOPRO-600-xx-L10POD-zz 

Testing: 

 

 

Options:

 

 

 

Manual Test 

zz = Blank 

 

Microwave Sensor (HI/LO) 

xx = SEN 

 

DALI Registered 

zz = DALI 

 

DALI Driver 

xx = DD 

 

Zoneworks 

zz = ZW 

 

 

 

 

Zoneworks HIVE 

zz = HV/HVG   

 

 

 

 

 

 

 

 

 

NOTE: Standard product codes with this symbol        are enabled with Clevertest Plus capability.   
Please refer to the operation guide supplied with the product for details. 

 

Spare Parts:

 

 

 

 

 

8002754

 

Replacement Emergency LED Board 

 

1330029 

Replacement 240V Driver

 

 

1330087 

Replacement 240V Driver 

(-SEN version only) 

 

1330038 

Replacement 240V Driver 

(-DD version only)

 

 

1530050 

Replacement Battery

 

 

AUM01370120001

 

Replacement Emergency Driver

 

 

AUM01870510001 

Replacement Emergency Driver 

(-SEN, -HV only)

 

 

 

 

Important: 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, 
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in 
accordance with the relevant Australian and International Standards. 

 

Note: This luminaire (with reinforced insulation between control/LED terminal and AC Supply) contains non-
user replaceable light source and battery 

– to be replaced (if required, refer installation instructions for 

battery replacement) by the manufacturer or his service agent or a similar qualified person. 
 
 

 

 

 

 

Reviews: