background image

1942122 

V1.4   

3 March 2020 

 

 

 

Clevertest and Clevertest Plus

 

Refer to the supplementary operation guide supplied with the Product.

 

 

 

After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or 

Red flashing for a period up to 2 minutes. 

 

 

Maintained fittings ((LWP2LIFE

M

-PRO-WPPOD-xx-yy)) cannot be scanned with a camera using 

the CleverSparky App as the maintained light source interferes with the camera scanning function. 

To register the fitting manually enter the serial number from the QR code and visually read the test 

result and enter manually into CleverSparky. 

 

 

Zoneworks and DATA Monitored Options

 

Lifelights with part numbers 

LWP2LIFE-PRO-WPPOD-ZW, LWP2LIFE-PRO-WPPOD-DATA 

are 

fitted with Zoneworks communications modules (nodes). These fittings are monitored using either 

Powerline Carrier Technology that utilising  the power cable to provide data communication or a 

dedicated data cable to/from data router installed on a dedicated data trunk connected to a central 

Server (can also be connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used 

to monitor, coordinate testing and collate test data from each Lifelight. Zoneworks Lifelights can be 

commissioned by a single push of the test switch, or scanning of the supplied barcode. The LED Test 

Switch indicator provides a multifunction indication of the status of the Lifelight during testing and 

normal operation: 

State

 

LED Operation

 

Commissioned 

LED on Solid (Green) 

Un-commissioned 

LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow) 

Emergency Light Test In Progress  LED flashes at 3s On (Yellow) & 0.5s Off 

 

In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the 

connection to the DATA network via a multi-drop bus (daisy chain connection).    For further 

information of installation of a Zoneworks system, please refer to the Zoneworks Users Guide and 

Commissioning Guide (incl. DATA version)   

 

DALI EM Option

 

Lifelights with part numbers LWP2LIFE-PRO-WPPOD

-DALI 

are fitted with DALI modules (nodes) 

that facilitate connection and integration to 3

rd

 Party Lighting Control Systems. Before installing the 

LWP2LIFE-PRO-WPPOD-DALI please confirm that the Lighting Control System has the capability 

to monitor DALI Emergency Luminaires. The LWP2LIFE-PRO-WPPOD-DALI will be addressed and 

configured into the control system by the Lighting Control System Commissioning Technicians and 

not Clevertronics.     

State

 

LED Operation

 

Commissioned/ Un-commissioned  LED on Solid (Green) 
Emergency Light Test in progress 

LED flashes at 1s On (Yellow) & 1s Off 

“IDENTIFY COMMAND” 

Fitting goes into emergency mode for 10 seconds 

 

A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network OR a 

5/6way “structured wiring system” lead and plug facilitating the power and DALI connection. DALI 

connections are marked as Da Da.   

   

 

 

   

 

 

 

 

   

 

 

 

 

 

 

 

Models: 

LWP2LIFEz-PRO-WPPOD-xx-yy

 

Testing: 

 

 

Options:

 

 

 

Manual Test 

 

xx = Blank 

 

Sustained 

z = Blank 

 

Zoneworks

 

xx = ZW 

 

Maintained 

z = M 

 

Z/W DATA   

 

xx = DATA 

 

Tamperproof 

yy =TP 

 

DALI Comp.     

 

xx = DALI 

 

 

 

 

Clevertest 

xx = CT     

 

 

 

 

(NOTE:  -CT  Products supplied with the  Clevertest Plus Symbol      are activated with Clevertest PLUS 

capability. Please refer to the operation guide supplied with the product for details). 

 

Spare Parts:   

1530050   

 

Battery, 3.3 Volt 2.5Ah Li-ion (4) 

2750356   

 

LP/L10 WP POD, Gen2, 2 LED, Wht LED, Sub Assy 

LLIFE-PRO-CKIT-NP 

LifelightPro,Control Only,Batten,L10, NP

 

Important:

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, 
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in 
accordance with the relevant Australian and International Standards. 

LWP2LIFE-PRO-WPPOD 

Surface Mount Twin Head Emergency Luminaire 

Installation & Maintenance Instruction Leaflet

 

Victoria (Head Office & Manufacturing) 

Website:

 

www.clevertronics.com.au

 

Email:

 

info@clevertronics.com.au

 

Phone:

 +61 3 9559 2700   

Fax:

 +61 3 9559 2799 

New South Wales

 

Phone:

 +61 2 8805 6400 

Fax:

 +61 2 8805 6444

 

Queensland

   

Phone:

 +61 7 3442 9700 

Fax:

 +61 7 3442 9777 

 

South Australia/Northern Territory

   

Phone:

 +61 8 8301 8800 

Fax:

 +61 8 8351 8286 

 

Western Australia

   

Phone:

 +61 8 9248 3720 

Fax:

 +61 8 9248 3725 

 

New Zealand 

Phone:

 +64 800 548 448

 

 

 

 
 

Designed in Australia to comply with the 

requirements of AS2293.3: 2005 and AS/NZS 

CISPR15: 2011 

NOTE: Standard product codes with this symbol             

are enabled with Clevertest Plus capability.  Please 

refer to the operation guide supplied with the product for 

details. 

 

 

 

 

 

 

 

 

 

 