1942122
V1.4
3 March 2020
Clevertest and Clevertest Plus
Refer to the supplementary operation guide supplied with the Product.
After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or
Red flashing for a period up to 2 minutes.
Maintained fittings ((LWP2LIFE
M
-PRO-WPPOD-xx-yy)) cannot be scanned with a camera using
the CleverSparky App as the maintained light source interferes with the camera scanning function.
To register the fitting manually enter the serial number from the QR code and visually read the test
result and enter manually into CleverSparky.
Zoneworks and DATA Monitored Options
Lifelights with part numbers
LWP2LIFE-PRO-WPPOD-ZW, LWP2LIFE-PRO-WPPOD-DATA
are
fitted with Zoneworks communications modules (nodes). These fittings are monitored using either
Powerline Carrier Technology that utilising the power cable to provide data communication or a
dedicated data cable to/from data router installed on a dedicated data trunk connected to a central
Server (can also be connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used
to monitor, coordinate testing and collate test data from each Lifelight. Zoneworks Lifelights can be
commissioned by a single push of the test switch, or scanning of the supplied barcode. The LED Test
Switch indicator provides a multifunction indication of the status of the Lifelight during testing and
normal operation:
State
LED Operation
Commissioned
LED on Solid (Green)
Un-commissioned
LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow)
Emergency Light Test In Progress LED flashes at 3s On (Yellow) & 0.5s Off
In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the
connection to the DATA network via a multi-drop bus (daisy chain connection). For further
information of installation of a Zoneworks system, please refer to the Zoneworks Users Guide and
Commissioning Guide (incl. DATA version)
DALI EM Option
Lifelights with part numbers LWP2LIFE-PRO-WPPOD
-DALI
are fitted with DALI modules (nodes)
that facilitate connection and integration to 3
rd
Party Lighting Control Systems. Before installing the
LWP2LIFE-PRO-WPPOD-DALI please confirm that the Lighting Control System has the capability
to monitor DALI Emergency Luminaires. The LWP2LIFE-PRO-WPPOD-DALI will be addressed and
configured into the control system by the Lighting Control System Commissioning Technicians and
not Clevertronics.
State
LED Operation
Commissioned/ Un-commissioned LED on Solid (Green)
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
“IDENTIFY COMMAND”
Fitting goes into emergency mode for 10 seconds
A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network OR a
5/6way “structured wiring system” lead and plug facilitating the power and DALI connection. DALI
connections are marked as Da Da.
Models:
LWP2LIFEz-PRO-WPPOD-xx-yy
Testing:
Options:
Manual Test
xx = Blank
Sustained
z = Blank
Zoneworks
xx = ZW
Maintained
z = M
Z/W DATA
xx = DATA
Tamperproof
yy =TP
DALI Comp.
xx = DALI
Clevertest
xx = CT
(NOTE: -CT Products supplied with the Clevertest Plus Symbol are activated with Clevertest PLUS
capability. Please refer to the operation guide supplied with the product for details).
Spare Parts:
1530050
Battery, 3.3 Volt 2.5Ah Li-ion (4)
2750356
LP/L10 WP POD, Gen2, 2 LED, Wht LED, Sub Assy
LLIFE-PRO-CKIT-NP
LifelightPro,Control Only,Batten,L10, NP
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant Australian and International Standards.
LWP2LIFE-PRO-WPPOD
Surface Mount Twin Head Emergency Luminaire
Installation & Maintenance Instruction Leaflet
Victoria (Head Office & Manufacturing)
Website:
Email:
info@clevertronics.com.au
Phone:
+61 3 9559 2700
Fax:
+61 3 9559 2799
New South Wales
Phone:
+61 2 8805 6400
Fax:
+61 2 8805 6444
Queensland
Phone:
+61 7 3442 9700
Fax:
+61 7 3442 9777
South Australia/Northern Territory
Phone:
+61 8 8301 8800
Fax:
+61 8 8351 8286
Western Australia
Phone:
+61 8 9248 3720
Fax:
+61 8 9248 3725
New Zealand
Phone:
+64 800 548 448
Designed in Australia to comply with the
requirements of AS2293.3: 2005 and AS/NZS
CISPR15: 2011
NOTE: Standard product codes with this symbol
are enabled with Clevertest Plus capability. Please
refer to the operation guide supplied with the product for
details.