Testing:
Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24
hours. Conduct the following tests:
•
For the first test, the emergency lamp must remain illuminated for at least 2 hours after disconnection
from the mains supply.
•
Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails to
remain illuminated for the requisite time, remedial action must be taken to repair the situation and
once completed, the unit must pass a subsequent test. For more specific information, please refer to
the current edition of the AS/NZS 2293.2 and AS/NZS 60598.2.22 Standards.
•
Clevertronics recommend scheduled PCA LED Light and battery changes at 4 yearly intervals or as
determined by regular testing.
Trouble Shooting:
Below are a list of common problems and their possible causes.
Fault:
The Green LED Test Switch indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault:
Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault:
Lamp illuminates in emergency mode, but only stays on for a short period.
Check:
Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1 (refer to
spacing tables for installation positions):
C0=D4
C90=E8 (Except –TH version)
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The Li-ion battery in this fitting has been selected to give excellent long life
performance in a controlled AS/NZS 60598.2.22 testing environment. Excessive battery cycling will
reduce through-life performance and may lead to premature battery failure. Battery warranty claims, as a
result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms.
The luminaire is not suitable for covering with thermally insulated material.
Warranty:
The manufacturer warrants the goods against defects solely due to faulty parts or workmanship of the
manufacturer for a period of 24 months from the date of purchase. This warranty covers the repair or
replacement of the goods at the discretion of the manufacturer, upon the goods being returned to the
nearest branch of the manufacturer at the clients cost. Any other warranty or guarantee, expressed or
implied, to the extent permitted by law, is expressly excluded. The manufacturer shall not be liable for any
costs or consequential losses that may arise through the use of any of the manufacturers’ products.
Installation or operation of this product in a manner NOT complying with this instruction leaflet will
automatically void any and all warranties.
Victoria (Head Office & Manufacturing)
195 Chesterville Rd
Moorabbin VIC 3189
Phone: +61 3 9559 2700
Fax: +61 3 9559 2799
New South Wales
Phone: +61 2 8805 6400
Fax: +61 2 8805 6444
Queensland
Phone: +61 7 3442 9700
Fax: +61 7 3442 9777
South Australia/Northern Territory
Phone: +61 8 8301 8800
Fax: +61 8 8351 8286
Western Australia
Phone: +61 8 9248 3720
Fax: +61 8 9248 3725
Models:
CCFPRO-ZZ-XXX-SS
Testing Options ZZ -CT
LP Clever-test Cleverfit Pro LED Exit
-ZW
LP Zoneworks Cleverfit Pro LED Exit
-DATA
LP Zoneworks DATA Cleverfit Pro LED Exit
-DALI
LP Zoneworks DALI Cleverfit Pro LED Exit
Body Colour XXX - BLK
Black Body
Theatre SS -TH Theatre Exit
Spare Parts:
1550130 – BATT:LP 3.2V 1500mAh 260mm lead,no BRKT.
8002550– PCA: LED Driver Cleverfit PRO
8002250 – PCA: LED Light Cleverfit PRO
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before
installation, ensure that the electricity supply has been switched off and isolated. Installation must be
carried out in accordance with the relevant Australian and International Standards.
V1.4 1943975 March 2017
LP Cleverfit Pro LED Exit
Installation & Maintenance Instruction Leaflet
Designed in Australia in accordance with;
AS/NZS2293.3:2005