background image

   
 

 

 
   

Testing:

 

 
Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 
 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after disconnection 
from the mains supply. 

 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails to 
remain illuminated for the requisite time, remedial action must be taken to repair the situation and 
once completed, the unit must pass a subsequent test. For more specific information, please refer to 
the current edition of the AS/NZS 2293.2 and AS/NZS 60598.2.22 Standards. 

 

 

Clevertronics recommend scheduled PCA LED Light and battery changes at 4 yearly intervals or as 
determined by regular testing. 

 

Trouble Shooting: 

 

Below are a list of common problems and their possible causes. 

 

Fault:   

The Green LED Test Switch indicator is not illuminated.

 

Check:    A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:   

Lamp does not illuminate in emergency mode. 

 

Check:    A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:   

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer to 
spacing tables for installation positions):

 

 

 

C0=D4 

C90=E8 (Except –TH version) 

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The Li-ion battery in this fitting has been selected to give excellent long life 
performance in a controlled AS/NZS 60598.2.22 testing environment. Excessive battery cycling will 
reduce through-life performance and may lead to premature battery failure. Battery warranty claims, as a 
result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms. 
 
The luminaire is not suitable for covering with thermally insulated material. 
 

Warranty:

 

The manufacturer warrants the goods against defects solely due to faulty parts or workmanship of the 
manufacturer for a period of 24 months from the date of purchase. This warranty covers the repair or 
replacement of the goods at the discretion of the manufacturer, upon the goods being returned to the 
nearest branch of the manufacturer at the clients cost. Any other warranty or guarantee, expressed or 
implied, to the extent permitted by law, is expressly excluded. The manufacturer shall not be liable for any 
costs or consequential losses that may arise through the use of any of the manufacturers’ products. 
Installation or operation of this product in a manner NOT complying with this instruction leaflet will 
automatically void any and all warranties. 

Victoria (Head Office & Manufacturing) 

195 Chesterville Rd 

Moorabbin VIC 3189   

Phone: +61 3 9559 2700   

Fax: +61 3 9559 2799 

New South Wales

 

Phone: +61 2 8805 6400 

Fax: +61 2 8805 6444 

Queensland

   

Phone: +61 7 3442 9700 

Fax: +61 7 3442 9777 

 

South Australia/Northern Territory

   

Phone: +61 8 8301 8800 

Fax: +61 8 8351 8286 

 

Western Australia

   

Phone: +61 8 9248 3720 

Fax: +61 8 9248 3725 

 

 

 

 
 

Models: 

CCFPRO-ZZ-XXX-SS

 

 

 

 

Testing Options ZZ -CT 

LP Clever-test Cleverfit Pro LED Exit 

 

 

-ZW 

LP Zoneworks Cleverfit Pro LED Exit 

-DATA 

LP Zoneworks DATA Cleverfit Pro LED Exit 

-DALI 

LP Zoneworks DALI Cleverfit Pro LED Exit 

Body Colour XXX  - BLK 

Black Body 

    Theatre    SS    -TH     Theatre Exit 

 

Spare Parts:   

1550130 – BATT:LP 3.2V 1500mAh 260mm lead,no BRKT. 

8002550– PCA: LED Driver Cleverfit PRO 

8002250 – PCA: LED Light Cleverfit PRO 

 

Important:

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before 

installation, ensure that the electricity supply has been switched off and isolated. Installation must be 

carried out in accordance with the relevant Australian and International Standards.

   

V1.4         1943975      March 2017 

LP Cleverfit Pro LED Exit 

 

Installation & Maintenance Instruction Leaflet

 

 

 

Designed in Australia in accordance with; 
AS/NZS2293.3:2005 

 

 

Reviews: