ClimaCheck Gateway NX400 Hardware Manual
–
2020-03-26 Page 14 of 41
3.2
View all values
All values, from internal inputs and external units connected through Modbus, can be seen on the
Show values menu. The list of values varies depending on the number of power meters, R560
modules and other external units that are configured.
To view all values:
•
Press ESC to enter the Main menu
•
Press Down until “Monitor”
appears in the display
•
Press SEL to enter Monitor menu
•
“Show values” appears in the display
•
Press OK
Values are shown with one sensor/value on each row with Comment/Description, sensor reading
and unit. Press Up/Down to step through the list of values.
Figure 7
, “View all values” menu
3.3
Send interval / Intense send
When ClimaCheck Online is used data is sent to the ClimaCheck server once every minute when
the compressor is on and every 5 minutes
when the compressor is off. To activate “intense send”
and send data every 15 second:
•
Press ESC to enter the Main menu
•
Press Down until “Monitor”
appears in the display
•
Press SEL to enter Monitor menu
•
Press
down until “Intense send” is showed in the display
•
Press OK
•
“Intense Send Active” appears
Intense send is automatically switched off after 15 minutes.
3.4
Signal level
GPRS/WiFi signal strength can be seen in the display of the unit as bars, see section 1.2. To view
the value in % or dBm:
•
Press ESC to enter the Main menu
•
Press Down until “Monitor”
appears in the display
•
Press SEL to enter Monitor menu
•
Press Down unt
il “Signal level GPRS”
or “Signal level
WiFi
”
is showed in the display
•
Press OK
Signal strength is presented in dBm and %. For reliable data transmission a signal strength above
2 “bars”
, -80dBm or 40% is required.