ClimaCheck Gateway NX400 Hardware Manual
–
2020-03-26 Page 18 of 41
•
Sensors has been connected/configured on the wrong position
Clear all configured sensors and connect them again, see section 3.7.4
•
A configured 1-Wire sensor is showing -999.00
NX400 has lost connection with the sensor, check wiring.
3.8
Reboot and Reload Configuration
Most of the configuration for external units can be done on the ClimaCheck server. Changes to
Modbus addresses for external units such as energy meters or R560 modules can be done on the
ClimaCheck Online server and then downloaded to the unit. If the unit has an internet connection
it will try to contact the server every 6 hour to check for commands to Reload configuration from
the server or Restart.
The unit can also be restarted or forced to reload configuration from the Setup menu.
3.9
Reload configuration from ClimaCheck Online server
Make sure the unit has internet connection and then:
•
Press ESC to enter the Main menu
•
Press Down until “Setup”
appears in the display
•
Press SEL to enter setup menu
•
Press Down until “Get Config Online” is showed in the display
•
Press OK to load configuration from CC Online server
•
“Waite for
config, Loading..
”
appears in the display
After a few seconds, when the configuration has been updated, the unit will go back to the initial
view.
All configuration made locally with the PA Pro Configurator, section 4, will be overwritten with the
configuration from the server.
3.10
Reboot
To restart the unit:
•
Press ESC to enter the Main menu
•
Press Down until “Setup”
appears in the display
•
Press SEL to enter setup menu
•
Press Down until “Restart/Reboot” is showed in the display
•
Press OK
The unit will reboot.
3.11
Set network interface
Network interface used by the Gateway to communicate with internet (ClimaCheck Online server)
can be set on the network interface menu. To enter it
•
Press ESC to enter the Main menu
•
Press down until “
Network
Setup”
appears in the display
•
Press SEL to enter Network Setup menu
•
“Network Interface”
appears in the display
•
Press SEL
The Gateway will change view, at the top of the page the current selection is displayed as (Active
XXXX) where XXXX is GPRS, LAN, WiFi, non or DIP. Below 6 options are listed: