C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
66
Tranquility
®
Compact High Capacity (TC_L) Series
R e v. : O c t o b e r 5 , 2 0 2 1
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S
3500
BHP
1.16
1.23
1.29
1.36 1.42 1.48 1.54 1.60 1.66 1.73 1.79 1.85 1.92 2.01 2.09 2.17
Sheave/Mtr
A
A
A
A
A
A
A
A
A
C
C
C
C
E
E
E
RPM
780
815
845
880
910
940
970
1000 1025 1055
1080
1105
1130
1160
1185
1210
Turns Open
5.5
5
4.5
3.5
3
2.5
2
1.5
1
4.5
4
3.5
3
2.5
2
1.5
3600
BHP
1.24
1.30
1.37
1.44 1.51 1.58 1.65 1.72 1.78 1.86 1.92 1.98 2.06 2.13 2.21 2.29
Sheave/Mtr
A
A
A
A
A
A
A
A
A
C
C
C
E
E
E
E
RPM
795
825
860
890
920
950
980
1010
1035
1065 1090 1115 1145 1165 1190 1215
Turns Open
5.5
4.5
4
3.5
3
2.5
2
1.5
1
4
3.5
3
2.5
2.5
2
1.5
3700
BHP
1.34
1.40
1.46
1.53 1.61 1.68 1.75 1.82 1.90 1.97 2.06 2.13 2.21 2.28 2.36 2.44
Sheave/Mtr
A
A
A
A
A
A
A
A
C
C
E
E
E
E
E
E
RPM
820
850
880
910
940
970
1000 1025 1055
1080
1110
1135
1160
1180
1205
1230
Turns Open
5
4.5
3.5
3
2.5
2
1.5
1
4.5
4
3.5
3
2.5
2
1.5
1.5
3800
BHP
1.43
1.49
1.56
1.63 1.70 1.78 1.86 1.94 2.02 2.12 2.20 2.28 2.34 2.42 2.50 2.58
Sheave/Mtr
A
A
A
A
A
A
A
A
E
E
E
E
E
E
E
E
RPM
840
870
900
930
960
990 1020 1045
1070
1100 1125 1150
1170
1195 1220 1245
Turns Open
4.5
4
3.5
3
2.5
2
1.5
1
4
3.5
3
2.5
2.5
2
1.5
1
3900
BHP
1.58
1.64
1.71
1.78 1.85 1.93 2.01 2.09 2.19 2.27 2.35 2.41 2.49 2.57 2.65
Sheave/Mtr
A
A
A
A
A
A
D
D
E
E
E
E
E
E
E
RPM
865
890
920
950
980
1010
1035
1060 1090 1115 1140 1160
1185
1210
1235
Turns Open
4
4
3
2.5
2
1.5
1
1
4
3.5
3
2.5
2
1.5
1.5
4000
BHP
1.68
1.75
1.83
1.92 2.00 2.08 2.16 2.26 2.34 2.42 2.50 2.56 2.64 2.72 2.80
Sheave/Mtr
A
A
A
A
D
D
D
E
E
E
E
E
E
E
E
RPM
885
910
940
970
1000 1025 1050
1080
1105
1130
1155
1175
1200 1225 1250
Turns Open
4
3.5
2.5
2.5
2
1
1
4
3.5
3
2.5
2
2
1.5
1
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor Unit
factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
All Data is Wet Coil
SCFM
ESP
0.00
0.10
0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50
TC_L096 Blower Performance, Cont’d.
Table Continued from Previous Page