Electrical - Line Voltage
Table 4f: Tranquility
®
20 (TS) Series Electrical Data - (ECM Motor & Secondary Pump)
All TS Units with ECM Fan Motor
TS Units (ECM)
TS Units with ECM Fan Motor
and Secondary Pump
Model
Voltage
Code
Rated
Voltage
Voltage
Min/Max
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
Pump
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
QTY
RLA
LRA
018
G
208/230/60/1
197/254
1
9.0
48.0
3.9
12.9
15.2
20
0.4
13.3
15.6
20
E
265/60/1
239/292
1
8.4
40.0
3.2
11.6
13.7
20
0.7
12.3
14.4
20
024
G
208/230/60/1
197/254
1
13.5
58.3
3.9
17.4
20.8
30
0.4
17.8
21.2
30
E
265/60/1
239/292
1
9
54.0
3.2
12.2
14.5
20
0.7
12.9
15.2
20
H
208/230/60/3
197/254
1
7.1
55.4
3.9
11.0
12.8
15
0.4
11.4
13.2
20
F*
460/60/3*
414/506
1
3.5
28.0
3.2
6.7
7.6
15
0.7
7.4
8.3
15
030
G
208/230/60/1
197/254
1
12.8
64.0
3.9
16.7
19.9
30
0.8
17.5
20.7
30
E
265/60/1
239/292
1
10.9
60.0
3.2
14.1
16.8
25
0.7
14.8
17.5
25
H
208/230/60/3
197/254
1
8.3
58.0
3.9
12.2
14.3
20
0.8
13.0
15.1
20
F*
460/60/3*
414/506
1
5.1
28.0
3.2
8.3
9.6
15
0.7
9.0
10.3
15
036
G
208/230/60/1
197/254
1
16.0
77.0
3.9
19.9
23.9
35
0.8
20.7
24.7
40
E
265/60/1
239/292
1
12.2
72.0
3.2
15.4
30.7
30
0.7
16.1
19.2
30
H
208/230/60/3
197/254
1
10
71.0
3.9
13.9
16.4
25
0.8
14.7
17.2
25
F*
460/60/3*
414/506
1
4.7
38.0
3.2
7.9
9.1
15
0.7
8.6
9.8
15
042
G
208/230/60/1
197/254
1
16.7
79.0
3.9
20.6
24.8
40
0.8
21.4
25.6
40
E
265/60/1
239/292
1
13.5
72.0
3.2
16.7
20.1
30
0.7
17.4
20.8
30
H
208/230/60/3
197/254
1
10.4
73.0
3.9
14.3
16.9
25
0.8
15.1
17.7
25
F*
460/60/3*
414/506
1
5.8
38.0
3.2
9.0
10.5
15
0.7
9.7
11.2
15
048
G
208/230/60/1
197/254
1
21.8
117.0
6.9
28.7
34.2
50
0.8
29.5
35.0
50
E
265/60/1
239/292
1
16.3
98.0
6.0
22.3
26.4
40
0.7
23.
27.1
40
H
208/230/60/3
197/254
1
13.7
83.1
6.9
20.6
24.0
35
0.8
21.4
24.8
35
F*
460/60/3*
414/506
1
6.2
41.0
6.0
12.2
13.8
20
0.7
12.9
14.5
20
060
G
208/230/60/1
197/254
1
26.4
134.0
6.9
33.3
39.9
60
1.1
34.4
41.0
60
E
265/60/1
239/292
1
19.9
130.0
6.0
25.9
30.9
50
1.3
27.2
32.2
50
H
208/230/60/3
197/254
1
16
110.0
6.9
22.9
26.9
40
1.1
24.0
28.0
40
F*
460/60/3*
414/506
1
7.8
52.0
6.0
13.8
15.8
20
1.3
15.1
17.1
20
070
G
208/230/60/1
197/254
1
30.8
178.0
6.9
37.7
45.4
70
1.1
37.9
45.6
70
H
208/230/60/3
197/254
1
19.6
138.0
6.9
26.5
31.4
50
1.1
27.6
32.5
50
F*
460/60/3*
414/506
1
8.2
66.1
6.0
14.2
16.3
20
1.3
15.5
17.6
25
* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with ECM motors/internal secondary circulators require a four wire power supply with neutral.
ECM motors/internal secondary circulators are rated 265 vac and are wired between one hot leg and neutral.