30
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tr a n q u i l i t y
®
2 0 ( T S ) S e r i e s
R e v. : 0 6 / 1 7 / 1 5
TS Blower Performance Data - (ECM Motor) - Standard Unit - No Reheat
Tranquility
®
20 (TS) Series with ClimaDry
®
Reheat Option (ECM Motor) -
All Tranquility
®
20 (TS) units with optional
ECM fan motor automatically adjusts for the reheat coil. The small additional pressure drop of the reheat coil causes
the ECM motor to slightly increase RPM to overcome the added pressure drop, and maintain selected CFM up to the
maximum ESP.
Unit minimum entering air temperature while in the dehumidifi cation, cooling, or continuous fan modes is
65ºF DB/55ºF WB
. Operation below this minimum may result in nuisance faults.
Residential
Units Only
Model
Max
ESP
(in. wg)
Fan
Motor
(hp)
Tap
Setting
Cooling Mode
Dehumid Mode
Heating Mode
AUX
CFM
Aux/
Emerg
Mode
Stg 1
Stg 2
Fan
Stg 1
Stg 2
Fan
Stg 1
Stg 2
Fan
018
1.0
1/2
4
640
800
400
500
620
400
640
800
400
4
800
3
600
750
375
470
590
375
600
750
375
3
750
2
525
650
330
400
500
330
525
650
330
2
650
1
450
550
280
450
550
280
1
650
024
1.0
1/2
4
900
1100
470
610
740
470
900
1100
470
4
1100
3
780
950
420
540
660
420
780
950
420
3
950
2
670
825
360
490
600
360
670
825
390
2
820
1
550
675
300
550
675
340
1
690
030
1.0
1/2
4
920
1130
560
720
880
560
1000
1230
560
4
1230
3
820
1000
500
640
780
500
900
1100
500
3
1100
2
740
900
450
580
700
450
800
950
450
2
950
1
660
800
400
640
780
400
1
780
036
0.90
1/2
4
1150
1400
700
900
1090
700
1150
1400
700
4
1400
3
1020
1250
630
800
980
630
1020
1250
630
3
1350
2
890
1080
540
690
840
540
890
1080
540
2
1350
1
740
900
450
750
920
450
1
1350
042
0.90
1/2
4
1290
1580
790
1010
1230
790
1290
1580
790
4
1580
3
1150
1400
700
900
1090
700
1150
1400
700
3
1400
2
1050
1280
640
820
1000
640
1020
1240
640
2
1350
1
920
1120
560
900
1080
560
1
1350
048
1.0
1
4
1420
1730
870
1110
1350
870
1520
1850
865
4
1850
3
1270
1550
780
990
1210
780
1350
1650
775
3
1650
2
1180
1440
720
920
1120
720
1110
1350
720
2
1350
1
1050
1280
640
980
1250
640
1
1200
060
0.75
1
4
1680
2050
1030
1310
1600
1030
1870
2280
1030
4
2280
3
1500
1830
910
1170
1420
910
1680
2050
910
3
2050
2
1400
1700
850
1090
1330
850
1480
1800
850
2
1800
1
1300
1580
790
1270
1550
790
1
1550
070
0.75
1
4
1830
2230
1100
1420
1740
1100
1830
2230
1100
4
2230
3
1600
1950
980
1250
1520
980
1720
2100
980
3
2100
2
1440
1750
880
1120
1360
880
1670
1950
880
2
1950
1
1200
1580
790
1460
1780
790
1
1780
See ECM control section for details on setting taps.
Bold numbers indicate factory settings.
During Auxiliary operation the CFM will run at the higher of the Heating (Delay
jumper) or AUX settings.
Airfl ow is controlled within 5% up to the Max ESP shown with wet coil.
Do not select Dehumidifi cation mode if HP CFM is on setting 1.
All units AHRI/ISO/ASHRAE 13256-1 rated HP CFM Setting 3.
Airfl ow in CFM with wet coil and clean air fi lter