background image

40

C l i m a t e M a s t e r   W a t e r- S o u r c e   H e a t   P u m p s

C L I M A T E M A S T E R   W A T E R - S O U R C E   H E A T   P U M P S

Tr a n q u i l i t y

®

  2 0   ( T S )   S e r i e s

R e v. :   0 6 / 1 7 / 1 5

Description of
Operation

Status LED

(green)

Test LED

(yellow)

Fault LED 

(red)

Alarm Relay

Normal mode

On

-

Off

Open

Normal mode with UPS

On

-

Flashing Code 8

Cycle (closed 5 sec,

open 25 sec)

DXM is non-functional

Off

Off

Off

Open

Fault Retry

Slow Flash

-

Flashing fault code

Open

Lockout

Fast Flash

-

Flashing fault code

Closed

Test Mode

-

On

-

-

Night Setback

Flashing Code 2

-

-

-

ESD

Flashing Code 3

-

-

-

HP Fault

Slow Flash

-

Flashing Code 2

Open

LP Fault

Slow Flash

-

Flashing Code 3

Open

LT1 Fault

Slow Flash

-

Flashing Code 4

Open

LT2 Fault

Slow Flash

-

Flashing Code 5

Open

CO Fault

Slow Flash

-

Flashing Code 6

Open

Over/Under Voltages

Slow Flash

-

Flashing Code 7

Open (closed after 15

minutes)

Invalid  T-stat Inputs

Flashing Code 4

-

-

-

DXM Control -

 For detailed control information, see 

DXM AOM (part #97B0003N13), Lon controller AOM (part 
#97B0013N01) or MPC AOM (part # 97B0031N01).

-Slow Flash = 1 fl ash every 2 seconds
-Fast Flash = 2 fl ashes every 1 second
-Flash code 2 = 2 quick fl ashes, 10 second pause, 2 quick 
fl ashes, 10 second pause, etc.
-On pulse 1/3 second; off pulse 1/3 second

Field Selectable Inputs -

 Test mode: Test mode allows 

the service technician to check the operation of the 
control in a timely manner. By momentarily shorting the 
test terminals, the DXM control enters a 20 minute test 
mode period in which all time delays are sped up 15 
times. Upon entering test mode, the status LED will fl ash 
a code representing the last fault. For diagnostic ease at 
the thermostat, the alarm relay will also cycle during test 
mode. The alarm relay will cycle on and off similar to the 
status LED to indicate a code representing the last fault, 
at the thermostat. Test mode can be exited by shorting 
the test terminals for 3 seconds.

Retry mode:

 If the control is attempting a retry of a fault, 

the status LED will slow fl ash (slow fl ash = one fl ash every 
2 seconds) to indicate the control is in the process of 
retrying.

Field Confi guration Options -

 Note: In the following 

fi eld confi guration options, jumper wires should be 
clipped ONLY when power is removed from the DXM 
control.

Water coil low temperature limit setting:

 Jumper 

3 (JW3-LT1 Low Temp) provides fi eld selection of 
temperature limit setting for LT1 of 30°F or 10°F [-1°F or 
-12°C] (refrigerant temperature).

DXM Controls

Table 5b: DXM LED And Alarm Relay Operations

Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].
Air coil low temperature limit setting: Jumper 2 (JW2-
LT2 Low Temp) provides fi eld selection of temperature 
limit setting for LT2 of 30°F or 10°F [-1°F or -12°C] 

(refrigerant temperature). 

Note: This jumper

 

should only be clipped under extenuating 
circumstances, as recommended by 
ClimateMaster technical services.

Not Clipped = 30°F [-1°C]. Clipped = 10°F 
[-12°C].

Alarm relay setting: 

Jumper 4 (JW4-AL2 Dry) 

provides fi eld selection of the alarm relay 
terminal AL2 to be jumpered to 24VAC or to 
be a dry contact (no connection).
Not Clipped = AL2 connected to R.
Clipped = AL2 dry contact (no connection).

Low pressure normally open:

 Jumper 1 

(JW1-LP norm open) provides fi eld selection 
for low pressure input to be normally closed or 
normally open.

Not Clipped = LP normally closed. Clipped = LP normally 
open. 

DIP Switches - Note: In the following fi eld 
confi guration options, DIP switches should only be 
changed when power is removed from the DXM 
control.

DIP Package #1 (S1) - 

DIP Package #1 has 8 switches 

and provides the following setup selections:

1.1 

- Unit Performance Sentinel (UPS) disable: DIP Switch 

1.1 provides fi eld selection to disable the UPS feature. 
On = Enabled. Off = Disabled.

1.2 -

 Compressor relay staging operation: DIP 1.2 

provides selection of compressor relay staging operation. 
The compressor relay can be selected to turn on with 
a stage 1 or stage 2 call from the thermostat. This 
is used with dual stage units (2 compressors where 
2 DXM controls are being used) or with master/
slave applications. In master/slave applications, 
each compressor and fan will stage according to 
its appropriate DIP 1.2 setting. If set to stage 2, the 
compressor will have a 3 second on-delay before 
energizing during a Stage 2 demand. Also, if set for stage 
2, the alarm relay will NOT cycle during test mode.
On = Stage 1. Off = Stage 2.

1.3 - 

Thermostat type (heat pump or heat/cool): DIP 1.3 

provides selection of thermostat type. Heat pump or 
heat/cool thermostats can be selected. When in heat/
cool mode, Y1 is the input call for cooling stage 1; Y2 is 
the input call for cooling stage 2; W1 is the input call for 
heating stage 1; and O/W2 is the input call for heating 
stage 2. In heat pump mode, Y1 is the input call for 

Summary of Contents for Tranquility 20 TSD 006 Series

Page 1: ...rmance Data ECM Motor Standard Unit No Reheat 30 TS Blower Performance Data Standard Unit No Reheat PSC Motor 31 TS Blower Performance Data Units with ClimaDry PSC Motor 32 ECM Blower Control 33 Typic...

Page 2: ...2 ClimateMaster Water Source Heat Pumps CL I MATEM ASTER WATER SOURCE HEAT PUMPS Tran q u i l i t y 20 TS Series Rev 06 17 15 This Page Intentionally Left Blank...

Page 3: ...06 012 E 265 60 1 N 575 60 3 F 460 60 3 AVAILABLE VOLTAGES 006 E G 009 E G 012 E G 018 E G 024 E F G H 030 E F G H 036 E F G H 042 E F G H N 048 E F G H N 060 E F G H N 070 F G H N OPTION 1 A J K 2 C...

Page 4: ...Application and Service Manual should be read and understood before attempting to service refrigerant circuits with HFC 410A Inspection Upon receipt of the equipment carefully check the shipment agai...

Page 5: ...g heat pumps General Information Pre Installation Installation Operation and Maintenance instructions are provided with each unit Horizontal equipment is designed for installation above false ceiling...

Page 6: ...x 20 406 x 508 24 x 24 610 x 610 28 x 24 711 x 610 28 x 24 711 x 610 28 x 30 711 x 762 2 16 x 30 2 406 x 762 2 16 x 30 2 406 x 762 1 16 x 30 1 20 x 30 1 406 x 762 1 508 x 762 1 16 x 30 1 20 x 30 1 40...

Page 7: ...should be given to access for easy removal of the filter and access panels Provide sufficient room to make water electrical and duct connection s If the unit is located in a confined space such as a...

Page 8: ...LW 3RZHU LVFRQQHFW 3RZHU LULQJ QVXODWHG VXSSO GXFW ZLWK DW OHDVW RQH GHJ HOERZ WR UHGXFH DLU QRLVH 5HWXUQ LU 6XSSO LU 8QLW DQJHU PP WKUHDGHG URGV 8QLW 3RZHU OH LEOH XFW RQQHFWRU 2SWLRQDO RZ 3UHVVXUH U...

Page 9: ...ft out the access panel and set aside Lift and rotate the discharge panel to the other position as shown being careful with the blower wiring 3 Check blower wire routing and connections for tension or...

Page 10: ...ED IN THE DRAIN LINE IT MUST BE LOCATED AFTER THE TRAP IN THE DIRECTION OF THE CONDENSATE FLOW Duct System Installation Proper duct sizing and design is critical to the performance of the unit The duc...

Page 11: ...vered door etc Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit Refer to Figures 7 and 8 for typical installation illus...

Page 12: ...low for proper drainage This connection must meet all local plumbing building codes Vertical units utilize a condensate hose inside the cabinet as a trapping loop therefore an external trap is not nec...

Page 13: ...mperature drops below the dew point insulation is required for ground loop applications in most climates Pipe joint compound is not necessary when Teflon thread tape is pre applied to hose assemblies...

Page 14: ...lve and or J type swivel connection Balancing valves and an external low pressure drop solenoid valve for use in variable speed pumping systems may also be included in the hose kit The piping system s...

Page 15: ...your local sales office should be consulted to determine the antifreeze best suited to your area Freeze protection should be maintained to 15 F 9 C below the lowest expected entering loop temperature...

Page 16: ...umps CL I MATEM ASTER WATER SOURCE HEAT PUMPS Tran q u i l i t y 20 TS Series Rev 06 17 15 Ground Loop Heat Pump Applications Figure 13 Typical Ground Loop Application High and Low Voltage Knockouts V...

Page 17: ...iping may cause failure of the PVC CPVC PVC CPVC piping should never be used as supply or return water piping with water source heat pump products containing HFC 410A as system failures and property d...

Page 18: ...sired flow of 1 5 to 2 gpm per ton 2 0 to 2 6 l m per kW is achieved A second method of flow control requires a flow control device mounted on the outlet of the water control valve The device is typic...

Page 19: ...oride Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion and Clogging Particula...

Page 20: ...1 0 1 7 7 9 9 5 15 1 3 9 0 10 6 15 N 575 60 3 518 633 1 4 8 33 0 1 4 6 2 7 4 15 N A N A N A N A 060 G 208 230 60 1 197 254 1 26 4 134 0 3 8 30 2 36 8 60 1 1 31 3 37 9 60 H 208 230 60 3 197 254 1 16 11...

Page 21: ...0 6 1 7 4 15 0 7 6 8 8 1 15 036 G 208 230 60 1 197 254 1 16 0 77 0 2 2 18 2 22 2 35 0 8 19 0 23 0 35 E 265 60 1 239 292 1 12 2 72 0 1 7 13 9 17 0 25 0 7 14 6 17 7 25 H 208 230 60 3 197 254 1 10 71 0...

Page 22: ...1 10 71 0 3 9 13 9 16 4 25 0 8 14 7 17 2 25 F 460 60 3 414 506 1 4 7 38 0 3 2 7 9 9 1 15 0 7 8 6 9 8 15 042 G 208 230 60 1 197 254 1 16 7 79 3 9 20 6 24 8 40 0 8 21 4 25 6 40 E 265 60 1 239 292 1 13...

Page 23: ...7 4 15 0 7 6 8 8 1 15 036 G 208 230 60 1 197 254 1 16 0 77 0 1 8 17 8 21 8 35 0 8 18 6 22 6 35 E 265 60 1 239 292 1 12 2 72 0 2 0 14 2 17 3 25 0 7 14 9 18 0 30 H 208 230 60 3 197 254 1 10 71 0 1 8 11...

Page 24: ...1 12 2 72 0 1 7 13 9 29 2 25 0 7 14 6 17 7 25 H 208 230 60 3 197 254 1 10 71 0 2 2 12 2 14 7 25 0 8 13 0 15 5 25 F 460 60 3 414 506 1 4 7 38 0 1 0 5 7 6 9 15 0 7 6 4 7 6 15 042 G 208 230 60 1 197 254...

Page 25: ...12 2 72 0 3 2 15 4 30 7 30 0 7 16 1 19 2 30 H 208 230 60 3 197 254 1 10 71 0 3 9 13 9 16 4 25 0 8 14 7 17 2 25 F 460 60 3 414 506 1 4 7 38 0 3 2 7 9 9 1 15 0 7 8 6 9 8 15 042 G 208 230 60 1 197 254 1...

Page 26: ...gure 16 Most ClimateMaster units are shipped on the medium speed tap Consult submittal data or engineering design guide for specific unit airflow tables Typical unit design delivers rated airflow at n...

Page 27: ...Selection The CXM DXM control allows the field selection of low water or water antifreeze solution temperature limit by clipping jumper JW3 which changes the sensing temperature associated with therm...

Page 28: ...include 75VA transformer Figure 20 AVM Valve Wiring Figure 21 Taco SBV Valve Wiring C C Thermostat Y1 1 2 3 Y1 AVM Taco Valve Heater Switch Water Solenoid Valves An external solenoid valve s should b...

Page 29: ...te mounting holes and drill holes with a 3 16 5mm bit Install supplied anchors and secure plate to the wall Thermostat wire must be 18 AWG wire Representative thermostat wiring is shown in Figures 22a...

Page 30: ...500 900 1100 500 3 1100 2 740 900 450 580 700 450 800 950 450 2 950 1 660 800 400 640 780 400 1 780 036 0 90 1 2 4 1150 1400 700 900 1090 700 1150 1400 700 4 1400 3 1020 1250 630 800 980 630 1020 1250...

Page 31: ...LO 1321 1294 1263 1226 1182 1130 1064 980 871 729 042 HI 1400 960 1808 1759 1723 1680 1617 1524 1399 1247 1075 MED 1537 1518 1494 1459 1408 1338 1247 1134 1001 LO 1323 1309 1284 1246 1192 1122 1036 9...

Page 32: ...loss Example Reheat coil loss can be determined from the above table Coil velocity FPM Airflow CFM Face Area sq ft 1 TSH036 has a face area of 4 86 sq ft see physical data table 2 At 1 100 cfm coil ve...

Page 33: ...e speed tap setting to airflow in CFM Heating Settings The heating setting determines the heating CFM Tap 1 is the lowest CFM setting while tap 4 is the highest CFM setting Consult submittal data or s...

Page 34: ...ations catalog for the specific unit series and model to correlate speed tap to airflow in CFM The dehumidification mode can be enabled in two ways 1 Constant Dehumidification Mode When the dehumidifi...

Page 35: ...35 climatemaster com THE SMART SOLUTION FOR ENERGY EFFIC I E NC Y Tranquility 20 TS Ser ies R ev 0 6 1 7 1 5 Typical Wiring Diagram Units with CXM Board and ECM Fan Motor Single Phase...

Page 36: ...6 ClimateMaster Water Source Heat Pumps CL I MATEM ASTER WATER SOURCE HEAT PUMPS Tran q u i l i t y 20 TS Series Rev 06 17 15 Typical Wiring Diagram Units with CXM Board and PSC Fan Motor Single Phase...

Page 37: ...37 climatemaster com THE SMART SOLUTION FOR ENERGY EFFIC I E NC Y Tranquility 20 TS Ser ies R ev 0 6 1 7 1 5 Typical Wiring Diagram Units with DXM Board and PSC Fan Motor Three Phase...

Page 38: ...eMaster Water Source Heat Pumps CL I MATEM ASTER WATER SOURCE HEAT PUMPS Tran q u i l i t y 20 TS Series Rev 06 17 15 Typical Wiring Diagram Units with CXM Board ECM Fan Motor and MPC DDC CONTROLS SIN...

Page 39: ...o 24VAC or to be a dry contact no connection Not Clipped AL2 connected to R Clipped AL2 dry contact no connection DIP Switches Note In the following field configuration options DIP switches should onl...

Page 40: ...Jumper 3 JW3 LT1 Low Temp provides field selection of temperature limit setting for LT1 of 30 F or 10 F 1 F or 12 C refrigerant temperature DXM Controls Table 5b DXM LED And Alarm Relay Operations Not...

Page 41: ...on DIP 1 4 On Heat Pump Off Heat Cool 1 4 Thermostat type O B DIP 1 4 provides selection of thermostat type for reversing valve activation Heat pump thermostats with O output reversing valve energized...

Page 42: ...remain open for 30 continuous seconds during on cycle to be recognized as a low pressure fault If the low pressure switch is open for 30 seconds prior to compressor power up it will be considered a l...

Page 43: ...LED Diagnostic Features The LED on the CXM board advises the technician of the current status of the CXM control The LED can display either the current CXM mode or the last fault in memory if in test...

Page 44: ...n in 1st Stage Heating 2nd Stage Heating A simultaneous call from G Y1 and Y2 to the G Y1 and Y2 terminals of the DXM control board will bring the unit on in 2nd Stage Heating When the call is satisfi...

Page 45: ...ejection to the building loop Although the ClimaDry option will work fine with low EWTs overcooling of the space may result with well water systems or on rare occasions with ground loop geothermal sys...

Page 46: ...um levels the other two factors should be at normal levels to ensure proper unit operation Extreme variations in temperature and humidity and or corrosive water or air will adversely affect unit perfo...

Page 47: ...system and add trisodium phosphate in a proportion of approximately one pound per 150 gallons 8 kg per 1000 l of water or other equivalent approved cleaning agent Reset the boiler to raise the loop t...

Page 48: ...nal of the DXM controller as shown in figure 1 to energize the modulating three way dehumidifica tion valve Once energized the valve will take 45 75 seconds to fully shift Continue flushing during thi...

Page 49: ...and fittings see table 3 System flushing Verify that all hoses are connected end to end when flushing to ensure that debris bypasses the unit heat exchanger water valves and other components Water use...

Page 50: ...mparing the pressure drop across the heat exchanger to table 9 In S I units the formula is as follows HR kW TD x l s x 4 18 f Check air temperature drop across the air coil when compressor is operatin...

Page 51: ...al panel Exercise caution when working with energized equipment CAUTION Verify that ALL water control valves are open and allow water flow prior to engaging the compressor Freezing of the coax or wate...

Page 52: ...7 1 8 12 3 12 0 0 757 45 3 9 26 9 3 2 22 0 3 2 21 9 3 0 21 0 060 7 5 0 473 28 1 3 9 1 0 6 4 3 0 5 3 2 0 5 3 4 11 3 0 713 43 3 5 24 5 2 5 16 9 2 1 14 2 2 0 13 6 15 0 0 947 57 6 1 42 0 4 7 32 4 4 1 28...

Page 53: ...132 142 132 142 132 142 215 235 200 220 185 205 10 15 10 15 10 15 8 13 7 12 6 11 18 8 20 8 14 1 16 1 9 4 11 4 20 26 20 26 20 26 104 114 106 116 108 118 309 329 312 332 315 335 8 12 8 12 8 12 7 12 7 1...

Page 54: ...201 24 29 24 29 24 29 10 15 8 13 8 13 15 7 17 7 11 6 13 6 7 6 9 6 18 24 18 24 18 24 102 112 106 116 110 120 313 333 314 334 316 336 8 12 8 12 8 12 8 13 8 13 8 13 8 9 10 9 6 7 8 7 4 5 6 5 22 28 23 29...

Page 55: ...4 18 24 50 1 5 2 25 3 136 146 136 146 136 146 211 231 197 217 183 203 11 16 11 16 11 16 6 11 5 10 5 10 20 6 22 6 14 8 16 8 9 11 17 23 17 23 17 23 99 109 103 113 108 118 302 322 306 326 311 331 10 15 1...

Page 56: ...ethanol antifreeze solution 070 Full Load Cooling without HWG active Full Load Heating without HWG active Entering Water Temp F Water Flow GPM ton Suction Pressure PSIG Discharge Pressure PSIG Superhe...

Page 57: ...s must be clean to obtain maximum performance Filters should be inspected every month under normal operating conditions and be replaced when necessary Units should never be operated without a filter W...

Page 58: ...Check slope of unit toward outlet Poor venting Check vent location X Moisture on sensor Check for moisture shorting to air coil X X Plugged air filter Replace air filter x X Restricted Return Air Flo...

Page 59: ...low restrictions Too high of external static Check static vs blower table X Reduced or no water flow in cooling Check pump operation or valve operation setting Check water flow Adjust to proper flow r...

Page 60: ..._____________________ Sales Order No __________________________________________ In order to minimize troubleshooting and costly system failures complete the following checks and data entries before th...

Page 61: ...1 1 6 6 36 6 7 36 6 7 5 2 3 7 1 48 1 3 16 21 9 9 5 2 36 6 7 36 6 7 7 5 1 7 5 287 36 36 7 5 1 7 5 287 36 36 8VH IRU ZDWHU IRU DQWLIUHH H 7 5 5 5 6 6 1 3 6 1625 3 16 21 9 9 7 5 5 5 3 6 6 1 27 5 6 2 75 5...

Page 62: ...t of insuf cient or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated labor to...

Page 63: ...ge or insuffi cient performance as a result of insuffi cient or incorrect system design or the improper application installation or use of CM s products or 14 Electricity or fuel costs or any increase...

Page 64: ...ed 97B0075N06 97B0075N06 7300 S W 44th Street Oklahoma City OK 73179 Phone 405 745 6000 Fax 405 745 6058 climatemaster com ISO 9001 2008 Certified Quality First Always R M A N U F A C T U R E R CERTIF...

Reviews: