c l i m a t e m a s t e r.c o m
13
Tranquility
®
(TRL) Series
R e v. : N o v e m b e r 1 1 , 2 0 2 1
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Horizontal Installation, Cont’d.
Figure 2: Horizontal Unit Pitch
(by others)
Water In
Water Out
Optional Balancing Valve
Ball Valve with optional
integral P/T plug and strainer
Stainless steel braid hose
with integral "J" swivel
Building
Loop
Return Air
Supply Air
3/8" [10mm] threaded rods
Unit Power
Flexible Duct
Connector
Optional Low Pressure Drop Water
Control Valve
(can be internally mounted
on some models)
Insulated
Supply Duct
Thermostat
Wiring
Unit Hanger
Figure 3: Typical Horizontal Unit Installation
Air Coil -
To obtain maximum
performance, the air coil should be
cleaned before start-up. A 10% solution
of dishwasher detergent and water is
recommended for both sides of the coil.
A thorough water rinse should follow.
UV based anti-bacterial systems may
damage e-coated air coils.
Notice!
Installation Note - Ducted Return:
Many horizontal WSHPs are installed in a
return air ceiling plenum application (above
ceiling). All TRL products are equipped
with filter frames for ducted or non-ducted
returns. Canvas or flexible connectors
should also be used to minimize vibration
between the unit and ductwork.
1/4” (6.4mm) pitch
toward drain for drainage
Drain Connection