Duct Work Installation, Cont’d.
Size
Right/Left SA Opening Sizes
Back SA Opening
006-009
8 x 6 or 16 x 6
7 x 6
012-015
16 x 6 or 24 x 6
7 x 6
All dimensions shown in inches.
Table 1: Supply Air (SA) Opening Dimensional Data
Size
Number of
Openings
Minimum Sq. in.
Opening*
Maximum Sq. in.
Opening
Recommended Sq. in.
Opening
006-009
1 or 2
42
96
48
012-015
1 or 2
90
186
144
All dimensions shown in inches.
* Less than minimum SA open area will cause unit to trip on safeties.
Table 2: Supply Air (SA) Square Inches
Supply
Opening Area (in)
006 or 009
012 or 015
Straight
8x6
X
16x6
X
X*
24x6
X
St Back
8x6 + 7x6
X
X*
16x6 + 7x6
X
24x6 + 7x6
X
Back
7X6
X
Field Configured
-
X
X
* For sizes 012-015 this configuration will have internal static pressure losses up to 0.2. ClimateMaster recommends field
wiring to motor speed tap four for highest fan motor CFM performance.
Table 3: Supply Air Options