CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tranquility
®
(TRL) Series
R e v. : N o v e m b e r 1 1 , 2 0 2 1
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
34
Electrical – Low Voltage Wiring
Accessory Connections
When water valves or circulating pumps
are applied as field installed external to
the unit, a field accessory kit is required.
This kit includes a relay, wires, and
installation instructions. See figures 17
and 18 for wiring details.
Low Voltage VA Ratings
Component
VA
Typical Blower Relay
6 - 7
Typical Reversing Valve Solenoid
4 - 6
30A Compressor Contactor
6 - 9
Subtotal
16 - 22
+ CXM2 board (5 - 9 VA)*
21 - 31
Remaining VA for Accessories**
19 - 29
* Standard transformer for CXM2 board is 75VA.
Optional DDC controls.
** Add accessory relay for pump or mwv (optional) - 1.4 VA
Figure 17: CXM2 Connection
Figure 18: Field Installed Accessory Relay Connection