CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tranquility
®
(TRL) Series
R e v. : N o v e m b e r 1 1 , 2 0 2 1
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
46
Unit Starting and Operating Conditions
Operating Limits
Environment – Units are designed for
indoor installation only. Never install units
in areas subject to freezing or where
humidity levels could cause cabinet
condensation (such as unconditioned
spaces subject to 100% outside air).
Power Supply – A voltage variation of
+/– 10% of nameplate utilization voltage
is acceptable.
Determination of operating limits
is dependent primarily upon three
factors: 1) return air temperature. 2)
water temperature, and 3) ambient
temperature. When any one of these
factors is at minimum or maximum levels,
the other two factors should be at normal
levels to ensure proper unit operation.
Extreme variations in temperature and
humidity and/or corrosive water or air
will adversely affect unit performance,
reliability, and service life. Consult Table 7
for operating limits.
Commissioning Conditions
Starting conditions vary depending upon
model and are based upon the following
notes:
Notes:
1. Conditions in Table 8 are not normal
or continuous operating conditions.
Minimum/maximum limits are start-up
conditions to bring the building space
up to occupancy temperatures. Units
are not designed to operate under
these conditions on a regular basis.
2. Voltage utilization range complies
with AHRI Standard 110.
Table 7: Operating Limits
Operating Limits
TRL
Cooling
Heating
Air Limits
Min. ambient air, DB
45°F [7°C]
39°F [4°C]
Rated ambient air, DB
80.6°F [27°C]
68°F [20°C]
Max. ambient air, DB
130°F [54.4°C]
85°F [29°C]
Min. entering air, DB/WB
65/50°F [18/10°C]
45°F [7.2°C]
Rated entering air, DB/WB
80.6/66.2°F [27/19°C]
68°F [20°C]
Max. entering air, DB/WB
95/75°F [35/24°C]
80°F [27°C]
Water Limits
Min. entering water
30°F [-1°C]
20°F [-6.7°C]
Normal entering water
50-110°F [10-43°C]
30-70°F [-1 to 21°C]
Max. entering water
120°F [49°C]
90°F [32°C]
Normal Water Flow*
2.25 to 4.5 gpm/ton
[1.6 to 3.2 l/m per kW]
* Except when identified on model-specific performance envelop