c l i m a t e m a s t e r.c o m
47
Tranquility
®
(TRL) Series
R e v. : N o v e m b e r 1 1 , 2 0 2 1
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Unit Starting and Operating Conditions
Table 8: Building Commissioning Limits
Commissioning Limits
Cooling
Heating
Air Limits
Min. ambient air, DB
45°F [7°C]
39°F [4°C]
Rated ambient air, DB
80.6°F [27°C]
68°F [20°C]
Max. ambient air, DB
130°F [54.4°C]
85°F [29°C]
Min. entering air, DB/WB
50/45°F [10/7°C]
40°F [4.5°C]
Rated entering air, DB/WB
80.6/66.2°F [27/19°C]
68°F [20°C]
Max. entering air, DB/WB
110/83°F [43/28°C]
80°F [27°C]
Water Limits
Min. entering water
30°F [-1°C]
20°F [-6.7°C]
Normal entering water
50-110°F [10-43°C]
30-70°F [-1 to 21°C]
Max. entering water
120°F [49°C]
90°F [32°C]
Normal Water Flow
2.25 to 4.5 gpm/ton
[1.6 to 3.2 l/m per kW]