TSM/TSL Vertical Stack
R e v. : J a n u a r y 1 8 , 2 0 2 1
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
ECM-CV Blower Performance Data
Table 5: TSM/TSL with ECM-CV Motor
Airflow in CFM with wet coil and clean 1” fiberglass air filter.
All units AHRI/ISO/ASHRAE 13256-1 rated on CFM shown on performance data page.
If unit is dual voltage rated, then the airflow is rated at the lowest voltage, i.e. 208V for 208-230V units.
Shipped on default settings. C=Cooling; H=Heating; D=Dehumidification
Change from default setting with Service tool (ACDU03C) or Communicating thermostat (ATC32U03C).
Airflow is controlled within 7%, up to the max ESP.
TSL15-36 ramp default is 30 sec.
* - Stage 2 ECM CV motor speed is engaged with a thermostat Y2 call. TSM Series is only available with single-stage compressors.
Tranquility
Model
Setting
Cooling Mode
Heating Mode
Dehumid Mode
Continuous
Fan Only
Mode
Fan Motor
Stage 1
Fan Motor
Stage 2*
Fan Motor
Stage 1
Fan Motor
Stage 2*
Fan Motor
Stage 1
Fan Motor
Stage 2*
TSM/L09
Default
250
350
250
350
250
300
250
Min
250
250
250
250
250
250
250
Max
400
400
400
400
400
400
400
TSM/L12
Default
300
400
300
400
300
350
300
Min
300
300
300
300
300
300
300
Max
500
500
500
500
500
500
500
TSM/L15
Default
500
600
500
600
500
500
500
Min
500
500
500
500
500
500
500
Max
700
700
700
700
700
700
700
TSM/L18
Default
600
700
600
700
600
600
500
Min
600
600
600
600
500
500
500
Max
800
800
800
800
800
800
800
TSM/L24
Default
650
850
650
850
650
650
600
Min
650
650
650
650
600
600
600
Max
950
950
950
950
950
950
950
TSM/L30
Default
850
1000
900
1000
850
850
700
Min
850
850
900
900
800
800
700
Max
1100
1100
1100
1100
900
1100
1100
TSM/L36
Default
900
1200
900
1250
900
900
900
Min
900
900
900
900
900
900
900
Max
1250
1250
1350
1350
1250
1250
1250