C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S
TSM/TSL Vertical Stack
R e v. : J a n u a r y 1 8 , 2 0 2 1
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
44
Blower Performance Data – TSM24
Table 5e
All data is presented as lowest of nameplate voltage.
All data is shown wet coil with clean 1” filter.
All data is ran at 80°F DB and 67°F WB.
CFM Tolerance is 7%.
RPM/Watt Tolerance 10%.
Denotes Operation not recommended.
External Static Pressure (in. wg)
PSC - Low Static
Speed Tap
0.0
0.1
0.2
0.3
Low
RPM
Power (W)
CFM
Medium
RPM
640
690
750
820
Power (W)
236
227
217
208
CFM
690
670
640
590
High
RPM
710
760
820
880
Power (W)
297
285
272
260
CFM
860
840
810
770
ECM - Constant T
orque
Speed Tap
0.0
0.1
0.2
0.3
1
RPM
640
690
730
Power (W)
62
68
76
CFM
710
660
600
2
RPM
690
730
780
850
Power (W)
89
97
102
109
CFM
820
770
720
670
3
RPM
740
780
830
890
Power (W)
120
129
134
143
CFM
930
880
830
790
4
RPM
830
880
920
Power (W)
169
173
185
CFM
990
950
910
5
RPM
Power (W)
CFM
ECM - Constant V
olume
CFM
0.0
0.1
0.2
0.3
600
RPM
600
660
730
830
Power (W)
70
87
104
122
700
RPM
640
700
770
860
Power (W)
96
115
134
153
800
RPM
680
750
820
890
Power (W)
122
143
164
184
900
RPM
720
790
860
920
Power (W)
155
176
197
218
950
RPM
740
810
880
930
Power (W)
193
214
234
255