c l i m a t e m a s t e r.c o m
47
TSM/TSL Vertical Stack
R e v. : J a n u a r y 1 8 , 2 0 2 1
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Blower Performance Data – TSL09
Table 5h
External Static Pressure (in. wg)
PSC - High Static
Speed Tap
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Low
RPM
1000
1120
1210
1290
1380
Power (W)
145
139
132
125
119
CFM
350
340
320
290
270
Medium
RPM
1520
1570
1610
1650
Power (W)
162
151
139
127
CFM
Operation not recommended
430
390
340
280
High
RPM
1710
Power (W)
151
CFM
390
ECM - Constant T
orque
Speed Tap
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1
RPM
980
1080
1170
1260
1360
Operation not recommended
Power (W)
47
51
54
58
62
CFM
340
320
290
270
240
2
RPM
1060
1160
1230
1320
1390
1500
Power (W)
58
62
66
70
75
79
CFM
380
360
330
310
280
260
3
RPM
1230
1310
1390
1440
1530
1590
1650
Power (W)
79
84
88
92
97
101
105
CFM
400
380
360
340
320
290
270
4
RPM
1470
1480
1550
1630
1680
Power (W)
Operation not recommended
108
113
117
122
126
CFM
410
390
370
360
340
ECM - Constant
Volume
CFM
0.1
0.2
0.3
0.4
0.5
0.6
360
340
250
RPM
810
950
1100
1230
1370
1490
1560
1640
Power (W)
30
38
47
57
67
78
89
101
300
RPM
900
1050
1180
1300
1410
1520
1590
1660
Power (W)
38
48
58
69
81
93
105
118
350
RPM
1000
1140
1260
1380
1450
1540
1620
1690
Power (W)
50
62
73
85
98
110
124
137
400
RPM
1100
1230
1340
1450
1490
1570
Power (W)
65
79
92
105
119
132
All data is presented as lowest of nameplate voltage.
All data is shown wet coil with clean 1" filter.
All data is ran at 80°F DB and 67°F WB.
CFM Tolerance is 7%
RPM/Watt Tolerance 10%