3
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tr a n q u i l i t y
®
( T R ) S e r i e s
R e v. : N o v e m b e r 2 , 2 0 2 0
c l i m a t e m a s t e r. c o m
T R H
A
0 3 6
C
G
3 0 C L B S
1 2
3
4 5 6
7
8
9
10
11
12
13
14
15
TR = TRANQUILITY
®
HIGH EFFICIENCY 410A
MODEL TYPE
H = HORIZONTAL
CONFIGURATION
V = VERTICAL
006 - E,G
UNIT SIZE
009 - E,G
012 - E,G
015 - E,G
018 - E,G
024 - E,G, H, F
030 - E,G,H,F
036 - E,G,H,F
042 - G,H,F,N
048 - G,H,F,N
060 - G,H,F,N
REVISION LEVEL
A = CURRENT REVISION
VOLTAGE
CONTROLS
WATER CIRCUIT OPTIONS
L = LEFT RETURN
RETURN AIR OPTIONS
R = RIGHT RETURN
SUPPLY AIR OPTIONS
S = STANDARD
V = LEFT RETURN, STAINLESS STEEL DRAIN PAN
W = RIGHT RETURN, STAINLESS STEEL DRAIN PAN
0 = None
2 = HWG (Coil Only)
6 = HWG (Coil Only) w/Auto Flow Regulator 2.5 GPM/Ton
7 = HWG (Coil Only) w/Auto Flow Regulator 3.0 GPM/Ton
8 = Auto Flow Regulator 2.5 GPM/Ton
9 = Auto Flow Regulator 3.0 GPM/Ton
5 = Internal Secondary Pump
DXM2 CONTROLS REQUIRED FOR CLIMADRY OPTION
HYDRONIC HEAT ONLY OFFERED IN HORIZONTAL CONFIGURATION
HEAT EXCHANGER OPTIONS
Standard
Motorized Valve
Hydronic Heat
ClimaDry
®
Non Coated Air Coil
Tin-plated Air Coil
Copper Cupro-nickel Copper Cupro-nickel
C
T
E
H
Y
B
R
N
S
P
A
U
D
J
W
F
C = CXM
D = DXM2
L = CXM w/LON
M = DXM2 w/LON
N = CXM w/MPC
P = DXM2 w/MPC
w/DISCONNECT
A = CXM
B = DXM2
E = CXM w/LON
K = DXM2 w/LON
R = CXM w/MPC
S = DXM2 w/MPC
G = 208-230/60/1
E = 265/60/1
H = 208-230/60/3
F = 460/60/3
N = 575/60/3
AVAILABLE
VOLTAGES
Option Supply Configuration
Motor
T
B
Top
Back
TRV
TRH
PSC
PSC
S
Straight
TRH
PSC
V
TRV
PSC Hi Static
Y
TRH
Z
TRH
Top
Back
Straight
K
TRV
TRV
ECM-CV
P
TRH
W
1
2
3
DXM2 Controls Required for ECM-CV Fan Motors
TRH
TRH
TRH
Top
Back
Straight
Straight
Top
Back
PSC Hi Static
PSC Hi Static
ECM-CV
ECM-CV
ECM-CT
ECM-CT
ECM-CT
CABINET INSULATION
OPTION
1
A
J
K
2
C
L
M
3
E
N
P
1” FILTER
RAIL
RANGE ULTRA
QUIET
2” FILTER
RAIL
1” FILTER
FRAME
2” FILTER
FRAME
4
G
R
S
NO
YES
NO
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
Model Nomenclature - General Overview
ClimaDry
®
Option Notes:
1. Unit must have DXM2 control option. 460 volt unit units require a four wire power supply with neutral.
2. ClimaDry
®
may not be combined with motorized water valve, internal secondary circulating pump, or automatic flow
regulator options.
3. Unit minimum entering air temperature while in the dehumidification, cooling, or continuous fan modes is
65ºF DB/55ºF WB
. Operation below this minimum may result in nuisance faults.
4. A thermostat with dehumidification mode or thermostat and separate humidistat/dehumidistat is required for
activation and control of ClimaDry
®
.
5. Sizes 006, 009, 012, 015, 018, downflow units and 575 volt units are not eligible for ClimaDry
®
.
Note: Above model nomenclature is a general reference. Not all configurations are available on all models. Consult selection software for detailed information.
Summary of Contents for Tranquility TR Series
Page 2: ......