34
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tr a n q u i l i t y
®
( T R ) S e r i e s
R e v. : N o v e m b e r 2 , 2 0 2 0
C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s
Blower Performance Data – TR006
Rated
CFM
Min CFM
Motor
Type
Motor Speed
Setting
External Static Pressure (in. wg)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
225
150
PSC
Low
CFM
210
190
160
Medium
CFM
260
240
210
190
High
CFM
310
290
270
230
180
225
150
ECM -
Constant
Torque
1
RPM
944
1028
1114
1206
1297
Power (W)
22
24
25
28
30
CFM
225
207
187
169
150
2
RPM
1201
1280
1362
1441
1523
1608
1694
Power (W)
34
37
39
42
44
48
51
CFM
233
217
201
185
173
164
150
3
RPM
1324
1400
1476
1551
1628
1709
1786
Power (W)
43
45
48
51
54
58
61
CFM
241
227
212
200
188
179
168
4
RPM
1516
1588
1658
1730
1799
Power (W)
55
58
61
65
67
CFM
240
227
216
205
193
225
150
ECM -
Constant
Volume
Minimum CFM
RPM
763
933
1078
1201
1314
1417
1519
1615
1712
Power (W)
16
21
27
40
36
41
46
52
59
CFM
150
150
150
150
150
150
150
150
150
Default CFM
RPM
983
1102
1211
1319
1419
1516
1610
1708
1783
1817
Power (W)
29
35
41
47
53
60
67
76
81
77
CFM
225
225
225
225
225
225
225
225
225
225
Maximum CFM
RPM
1053
1162
1265
1366
1462
1553
1648
1733
1802
1817
Power (W)
35
41
47
53
60
67
76
84
88
78
CFM
250
250
250
250
250
250
250
250
250
250
See ECM control section for details on setting airflow.
Airflow is controlled within 5% up to the Max ESP shown with wet coil.
Do not select Dehumidification mode if HP CFM is on setting 1.
Black areas denote ESP where operation is not recommended.
PSC: Units factory shipped on medium speed. Other speeds require field selection.
CT ECM: Units factory shipped on Speed Tap 2 for Fan-Only and Speed Tap 3 for Heating/Cooling.
All airflow is rated and shown above at the lower voltage if unit is dual voltage rated, e.g. 208V for 208-230V units.
Only two speed fan (H & M) available on 575V units.
Performance stated is at the rated power supply. Performance may vary as the power supply varies from the rated.
All data is shown wet coil with clean 1” filter.
All data is ran at 80 °F DB and 67 °F WB.
CFM Tolerance is 7%.
RPM/Watt Tolerance 10%.