Blower Performance Data – TR009
Rated
CFM
Min CFM
Motor
Type
Motor Speed
Setting
External Static Pressure (in. wg)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
325
225
PSC
Low
CFM
340
322
300
260
Medium
CFM
390
360
320
290
260
High
CFM
410
380
350
320
280
325
225
ECM -
Constant
Torque
1
RPM
1137
1203
1266
1344
1413
Power (W)
40
42
44
47
49
CFM
294
278
259
245
230
2
RPM
1361
1413
1464
1503
1577
1640
1700
1751
1803
1831
Power (W)
67
70
73
74
79
82
85
88
90
85
CFM
370
357
343
326
318
302
291
278
265
235
3
RPM
1538
1589
1642
1695
1749
1812
1829
1847
Power (W)
86
88
91
95
98
101
96
90
CFM
370
358
346
334
322
307
280
247
4
RPM
1835
1853
1869
1875
Power (W)
120
113
107
102
CFM
340
309
276
234
325
225
ECM -
Constant
Volume
Minimum CFM
RPM
929
1083
1210
1324
1432
1529
1595
1723
1792
Power (W)
25
32
39
45
53
60
66
78
83
CFM
225
225
225
225
225
225
225
225
225
Default CFM
RPM
1209
1326
1430
1535
1635
1732
1792
1801
1811
Power (W)
49
58
67
77
88
100
105
95
88
CFM
325
325
325
325
325
325
325
325
325
Maximum CFM
RPM
1691
1753
1765
1769
1778
1784
1793
1803
1813
Power (W)
126
134
131
125
119
118
105
98
90
CFM
375
375
375
375
375
375
375
375
375
See ECM control section for details on setting airflow.
Airflow is controlled within 5% up to the Max ESP shown with wet coil.
Do not select Dehumidification mode if HP CFM is on setting 1.
Black areas denote ESP where operation is not recommended.
PSC: Units factory shipped on medium speed. Other speeds require field selection.
CT ECM: Units factory shipped on Speed Tap 2 for Fan-Only and Speed Tap 3 for Heating/Cooling.
All airflow is rated and shown above at the lower voltage if unit is dual voltage rated, e.g. 208V for 208-230V units.
Only two speed fan (H & M) available on 575V units.
Performance stated is at the rated power supply. Performance may vary as the power supply varies from the rated.
All data is shown wet coil with clean 1” filter.
All data is ran at 80 °F DB and 67 °F WB.
CFM Tolerance is 7%.
RPM/Watt Tolerance 10%.