37
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tr a n q u i l i t y
®
( T R ) S e r i e s
R e v. : N o v e m b e r 2 , 2 0 2 0
c l i m a t e m a s t e r. c o m
Blower Performance Data – TR015
Rated
CFM
Min CFM
Motor
Type
Motor Speed
Setting
External Static Pressure (in. wg)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
525
375
PSC
Low
CFM
503
490
479
439
Medium
CFM
595
575
562
510
451
High
CFM
581
510
386
525
375
PSC -
High
Static
Low
CFM
462
456
443
425
385
Medium
CFM
546
539
531
513
481
414
High
CFM
547
426
525
375
ECM -
Constant
Torque
1
RPM
655
614
701
770
851
937
Power (W)
67
55
62
68
75
82
CFM
648
588
542
493
441
378
2
RPM
655
720
799
863
946
1021
1078
Power (W)
67
74
81
87
95
102
108
CFM
648
608
557
514
460
402
354
3
RPM
687
744
822
883
950
1032
1098
1150
Power (W)
79
86
94
101
107
117
124
130
CFM
695
659
611
570
526
475
422
377
4
RPM
716
771
844
906
965
1037
1110
1170
1219
Power (W)
92
98
107
114
121
129
138
145
151
CFM
737
705
661
622
582
534
482
438
396
5
RPM
763
790
851
924
978
1039
1113
1175
1233
1281
Power (W)
106
110
117
126
133
141
151
159
165
172
CFM
745
745
708
662
626
585
535
488
444
402
525
375
ECM -
Constant
Volume
Minimum CFM
RPM
617
741
848
945
1028
1103
1171
Power (W)
36
52
68
84
99
114
129
CFM
375
375
375
375
375
375
375
Default CFM
RPM
661
767
859
944
1028
1107
1179
1247
Power (W)
55
74
90
108
127
147
166
186
CFM
525
525
525
525
525
525
525
525
Maximum CFM
RPM
586
695
795
882
963
1038
1111
1180
1248
1312
Power (W)
54
73
93
112
132
152
173
194
216
238
CFM
625
625
625
625
625
625
625
625
625
625
See ECM control section for details on setting airflow.
Airflow is controlled within 5% up to the Max ESP shown with wet coil.
Do not select Dehumidification mode if HP CFM is on setting 1.
Black areas denote ESP where operation is not recommended.
PSC: Units factory shipped on medium speed. Other speeds require field selection.
CT ECM: Units factory shipped on Speed Tap 2 for Fan-Only and Speed Tap 3 for Heating/Cooling.
All airflow is rated and shown above at the lower voltage if unit is dual voltage rated, e.g. 208V for 208-230V units.
Only two speed fan (H & M) available on 575V units.
Performance stated is at the rated power supply. Performance may vary as the power supply varies from the rated.
All data is shown wet coil with clean 1” filter.
All data is ran at 80 °F DB and 67 °F WB.
CFM Tolerance is 7%.
RPM/Watt Tolerance 10%.