47
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tr a n q u i l i t y
®
( T R ) S e r i e s
R e v. : N o v e m b e r 2 , 2 0 2 0
c l i m a t e m a s t e r. c o m
Blower Performance Data – TR Hybrid 012
Rated
CFM
Min CFM
Motor
Type
Motor Speed
Setting
External Static Pressure (in. wg)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
400
300
ECM -
Constant
Torque
1
RPM
1402
1449
1492
1539
1597
Power (W)
70
73
75
78
80
CFM
348
335
325
311
299
2
RPM
1524
1570
1604
1649
1690
1737
1794
Power (W)
90
93
97
100
103
107
110
CFM
377
374
365
354
345
335
317
3
RPM
1727
1765
1790
1794
1796
1802
1807
Power (W)
130
128
124
121
120
115
110
CFM
435
427
416
397
376
351
320
4
RPM
1760
1780
1784
1786
1796
1798
1816
Power (W)
140
137
132
130
122
117
110
CFM
445
432
416
391
376
354
324
400
300
ECM -
Constant
Volume
Minimum CFM
RPM
1318
1404
1487
1576
1667
1748
1831
1920
2006
2092
Power (W)
50
60
70
80
90
100
110
120
130
140
CFM
300
300
300
300
300
300
300
300
300
300
Default CFM
RPM
1648
1716
1787
1852
1913
1988
2059
2124
2192
2260
Power (W)
97
109
120
134
150
159
170
184
197
209
CFM
400
400
400
400
400
400
400
400
400
400
Maximum CFM
RPM
2023
2028
2032
2038
2045
2048
2052
2058
2063
2068
Power (W)
200
195
190
185
180
175
170
165
160
155
CFM
450
450
450
450
450
450
450
450
450
450
Interpolation is permissible; extrapolation is not.
All performance is based upon the lower voltage of dual voltage rated units.
Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
See performance correction tables for operating conditions other than those listed above.
Summary of Contents for Tranquility TR Series