48
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tr a n q u i l i t y
®
( T R ) S e r i e s
R e v. : N o v e m b e r 2 , 2 0 2 0
C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s
Blower Performance Data – TR Hybrid 015
Rated
CFM
Min CFM
Motor
Type
Motor Speed
Setting
External Static Pressure (in. wg)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
525
375
ECM -
Constant
Torque
1
RPM
838
902
974
1055
1126
Power (W)
83
90
96
103
110
CFM
589
549
505
452
393
2
RPM
935
996
1070
1146
1210
1266
Power (W)
107
110
118
126
132
137
CFM
618
561
517
460
411
371
3
RPM
1016
1081
1150
1233
1291
1338
Power (W)
125
132
141
149
155
159
CFM
615
576
529
471
428
386
4
RPM
1163
1241
1316
1365
1413
Power (W)
160
169
177
184
189
CFM
602
557
493
454
417
5
RPM
1252
1317
1391
1438
Power (W)
191
198
208
215
CFM
626
577
519
480
525
375
ECM -
Constant
Volume
Minimum CFM
RPM
723
793
813
934
1004
1074
1161
Power (W)
27
44
62
80
97
115
133
CFM
375
375
375
375
375
375
375
Default CFM
RPM
756
830
872
976
1049
1123
1207
1269
1343
Power (W)
53
76
99
121
143
166
189
211
234
CFM
525
525
525
525
525
525
525
525
525
Maximum CFM
RPM
777
851
924
1000
1078
1149
1221
1298
1372
1446
Power (W)
84
107
131
154
176
200
224
247
270
293
CFM
625
625
625
625
625
625
625
625
625
625
Interpolation is permissible; extrapolation is not.
All performance is based upon the lower voltage of dual voltage rated units.
Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
See performance correction tables for operating conditions other than those listed above.
Summary of Contents for Tranquility TR Series
Page 2: ......