Blower Performance Data – TR Hybrid 024
Rated
CFM
Min CFM
Motor
Type
Motor Speed
Setting
External Static Pressure (in. wg)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
800
600
ECM -
Constant
Torque
1
RPM
816
871
928
988
1045
1119
Power (W)
125
133
141
149
157
168
CFM
787
756
723
686
649
604
2
RPM
875
925
974
1030
1084
1137
1196
1271
1315
Power (W)
160
168
177
186
195
204
214
227
235
CFM
876
848
819
787
753
720
684
634
603
3
RPM
934
979
1026
1070
1124
1174
1224
1275
1339
1399
Power (W)
200
209
218
226
237
247
257
267
280
293
CFM
962
936
909
883
851
820
789
755
715
676
4
RPM
1083
1127
1167
1218
1263
1309
1355
1405
Power (W)
270
280
289
301
311
322
333
345
CFM
1004
980
954
925
896
867
838
807
5
RPM
1314
1357
1399
1444
Power (W)
380
391
403
416
CFM
1004
977
950
923
800
600
ECM -
Constant
Volume
Minimum CFM
RPM
766
833
899
967
1037
1101
1167
1235
1302
1369
Power (W)
80
99
118
136
154
174
193
211
229
248
CFM
600
600
600
600
600
600
600
600
600
600
Default CFM
RPM
890
950
1006
1071
1141
1192
1247
1312
1372
1433
Power (W)
148
172
194
218
244
265
287
312
335
359
CFM
800
800
800
800
800
800
800
800
800
800
Maximum CFM
RPM
1034
1088
1144
1195
1244
1302
1358
1409
1463
1516
Power (W)
256
285
316
343
368
401
432
459
488
517
CFM
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
Interpolation is permissible; extrapolation is not.
All performance is based upon the lower voltage of dual voltage rated units.
Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.