55
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tr a n q u i l i t y
®
( T R ) S e r i e s
R e v. : N o v e m b e r 2 , 2 0 2 0
c l i m a t e m a s t e r. c o m
Blower Performance Data – TR Hybrid 060
Rated
CFM
Min CFM
Motor
Type
Motor Speed
Setting
External Static Pressure (in. wg)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1950
1500
ECM -
Constant
Torque
1
RPM
856
886
916
946
978
Power (W)
448
462
476
490
505
CFM
1739
1693
1646
1595
1546
2
RPM
943
969
997
1026
1054
1081
1110
1140
1170
1199
Power (W)
622
637
654
670
687
702
719
736
753
770
CFM
1954
1915
1872
1828
1780
1736
1692
1648
1604
1562
3
RPM
1029
1053
1079
1106
1133
1159
1185
1210
1230
1250
Power (W)
833
850
868
887
906
925
943
960
957
953
CFM
2166
2126
2087
2045
2000
1954
1914
1872
1814
1755
4
RPM
1049
1073
1099
1125
1149
1169
1189
1208
1228
1248
Power (W)
897
915
934
952
963
959
955
952
948
946
CFM
2224
2186
2145
2107
2055
1988
1926
1864
1804
1745
5
RPM
Power (W)
CFM
1950
1500
ECM -
Constant
Volume
Minimum CFM
RPM
814
862
908
956
1006
1051
1097
1145
1192
1240
Power (W)
324
376
428
479
530
582
634
685
736
788
CFM
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
Default CFM
RPM
1046
1072
1093
1123
1158
1175
1196
Power (W)
854
872
874
908
956
943
945
CFM
1950
1950
1950
1950
1950
1950
1950
Maximum CFM
RPM
1078
1097
1116
Power (W)
955
950
946
CFM
2200
2200
2200
Interpolation is permissible; extrapolation is not.
All performance is based upon the lower voltage of dual voltage rated units.
Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
See performance correction tables for operating conditions other than those listed above.