All TT Units
TT Units with ClimaDry
®
TT Units with Secondary Pump
Model
Voltage
Code
Voltage
Min/Max
Voltage
Reheat
Pump
FLA
Total
Unit FLA
Min
Circuit Amp
Max
Fuse/HACR
Pump
FLA
Total
Unit FLA
Min
Circuit
Amp
Max
Fuse/
HACR
TT
026
G
208/230/60/1
197/252
0.8
16.4
19.3
30
0.8
16.4
19.3
30
E
265/60/1
239/292
0.7
13.0
15.3
20
0.7
13.0
15.3
20
H
208/230/60/3
197/252
0.8
11.2
12.8
15
0.8
11.2
12.8
15
F*
460/60/3
*
414/506
0.7
7.4
8.3
15
0.7
7.4
8.3
15
TT
038
G
208/230/60/1
197/252
0.8
20.0
23.8
35
0.8
20.0
23.8
35
H
208/230/60/3
197/252
0.8
16.3
19.2
30
0.8
16.3
19.2
30
F*
460/60/3
*
414/506
0.7
9.6
11.0
15
0.7
9.6
11.0
15
TT
049
G
208/230/60/1
197/252
0.8
29.2
34.5
50
0.8
28.9
34.2
50
H
208/230/60/3
197/252
0.8
22.0
25.5
35
0.8
21.7
25.2
35
F*
460/60/3
*
414/506
0.7
13.5
15.1
20
0.7
13.1
14.7
20
TT
064
G
208/230/60/1
197/252
1.1
35.1
41.8
60
1.1
35.1
41.8
60
H
208/230/60/3
197/252
1.1
24.5
28.6
45
1.1
24.5
28.6
45
F*
460/60/3
*
414/506
1.1
14.3
16.1
20
1.1
14.3
16.1
20
TT
072
G
208/230/60/1
197/252
1.1
37.7
45.1
70
1.1
37.7
45.1
70
H
208/230/60/3
197/252
1.1
25.6
30.0
45
1.1
25.6
30.0
45
F*
460/60/3
*
414/506
1.1
15.6
17.7
25
1.1
15.6
17.7
25
HACR circuit breaker in USA only
Wire length based on one way measurement with 2% voltage drop
Wire size based on 60°C copper conductor
All fuses Class RK-5
* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with ECM motors require a four wire power supply with neutral. ECM motor is rated 265
vac and is wired between one hot leg and neutral.
Table 4b: Tranquility
®
30 (TT) Series Electrical Data Units with Secondary Pump or ClimaDry
®
Reheat
Electrical - Line Voltage
Table 4a: Tranquility
®
30 (TT) Series Electrical Data (Standard Units)
All TT Units
Standard TT Units
Model
Voltage
Code
Voltage
Min/Max
Voltage
Compressor
Fan
Motor FLA
Total
Unit FLA
Min
Circuit Amp
Max
Fuse/
HACR
QTY
RLA
LRA
TT
026
G
208/230/60/1
197/252
1
11.7
58.3
3.9
15.6
18.5
30
E
265/60/1
239/292
1
9.1
54.0
3.2
12.3
14.6
20
H
208/230/60/3
197/252
1
6.5
55.4
3.9
10.4
12.0
15
F*
460/60/3
*
414/506
1
3.5
28.0
3.2
6.7
7.6
15
TT
038
G
208/230/60/1
197/252
1
15.3
83.0
3.9
19.2
23.0
35
H
208/230/60/3
197/252
1
11.6
73.0
3.9
15.5
18.4
30
F*
460/60/3
*
414/506
1
5.7
38.0
3.2
8.9
10.3
15
TT
049
G
208/230/60/1
197/252
1
21.2
104.0
6.9
28.1
33.4
50
H
208/230/60/3
197/252
1
14.0
83.1
6.9
20.9
24.4
35
F*
460/60/3
*
414/506
1
6.4
41.0
6.0
12.4
14.0
20
TT
064
G
208/230/60/1
197/252
1
27.1
152.9
6.9
34.0
40.8
60
H
208/230/60/3
197/252
1
16.5
110.0
6.9
23.4
27.5
40
F*
460/60/3
*
414/506
1
7.2
52.0
6.0
13.2
15.0
20
TT
072
G
208/230/60/1
197/252
1
29.7
179.2
6.9
36.6
44.0
70
H
208/230/60/3
197/252
1
17.6
136.0
6.9
24.5
28.9
45
F*
460/60/3
*
414/506
1
8.5
66.1
6.0
14.5
16.6
25
HACR circuit breaker in USA only
Wire length based on one way measurement with 2% voltage drop
Wire size based on 60°C copper conductor
All fuses Class RK-5
* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with ECM motors require a four wire power supply with neutral. ECM motor
is rated 265 vac and is wired between one hot leg and neutral.