15
c l i m a t e m a s t e r. c o m
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tr a n q u i l i t y
®
2 2 ( T Z ) S e r i e s
R e v i s e d : 0 1 / 2 1 / 1 3
Water Pressure Schrader Ports
The pressure ports built in to the unit are provided as a
means of measuring pressure drop through the water-to-
refrigerant heat exchanger. The water pressure ports are
schrader ports smaller than refrigerant schrader ports.
They are the same size as tire schrader ports. A digital
pressure gauge is recommended for taking pressure
vFlow™ Heat Pump Applications Overview - Continued
Low System Pressure Drop Valve
High System Pressure Drop Valve
Model
CV
MOPD
WPD Adders
GPM
PSI
FT
024
4.7
200
3.0
0.41
0.94
4.7
200
4.5
0.92
2.12
4.7
200
6.0
1.63
3.76
030
4.7
200
3.8
0.65
1.51
4.7
200
5.6
1.42
3.28
4.7
200
7.5
2.55
5.88
036
4.7
200
4.5
0.92
2.12
4.7
200
6.8
2.09
4.84
4.7
200
9.0
3.67
8.47
042
4.7
200
5.3
1.27
2.94
4.7
200
7.9
2.83
6.53
4.7
200
10.5
4.99
11.53
048
4.7
200
6.0
1.63
3.76
4.7
200
9.0
3.67
8.47
4.7
200
12.0
6.52
15.06
060
7.4
200
7.0
.89
2.06
7.4
200
10.5
2.01
4.64
7.4
200
14.0
3.58
8.26
Model
CV
MOPD
WPD Adders
GPM
PSI
FT
024
4.7
200
3.0
0.41
0.94
4.7
200
4.5
0.92
2.12
4.7
200
6.0
1.63
3.76
030
7.4
200
3.8
0.26
0.61
7.4
200
5.6
0.57
1.32
7.4
200
7.5
1.03
2.37
036
7.4
200
4.5
0.37
0.85
7.4
200
6.8
0.84
1.95
7.4
200
9.0
1.48
3.42
042
10.0
200
5.3
0.28
0.65
10.0
200
7.9
0.62
1.44
10.0
200
10.5
1.10
2.55
048
10.0
200
6.0
0.36
0.83
10.0
200
9.0
0.81
1.87
10.0
200
12.0
1.44
3.33
060
19.0
200
7.0
0.14
0.31
19.0
200
10.5
0.31
0.70
19.0
200
14.0
0.54
1.25
readings through these ports. The water fl ow through
the unit can be determined by measuring the water
pressure at the “water pressure out” port and subtracting
it from the water pressure at the “water pressure in” port.
Comparing the pressure differential to the pressure drop
table (wpd)/fl ow rate in Tables 15a through 15d in this
manual will determine the fl ow rate through the unit.
Standard Head Variable Pump Performance
UPM Geo 25-85 Pump Curve
UPM Geo 25-85 Pump Curve
0
5
10
15
20
25
30
35
0 5 10 15 20 25
Head (Ft.)
Flow (GPM)
GPM
Head (ft)
0.0
28.6
1.0
28.7
2.0
28.4
3.0
27.9
4.0
27.2
5.0
26.3
6.0
25.2
7.0
23.9
8.0
22.6
9.0
21.1
10.0
19.6
11.0
18.0
12.0
16.4
13.0
14.9
14.0
13.3
15.0
11.9
16.0
10.5
17.0
9.3
18.0
8.2
19.0
7.3
20.0
6.6
21.0
6.1