Horizontal Installation
Figure 3: Typical Horizontal Unit Installation
Air Coil
- To obtain maximum performance, the air coil
should be cleaned before start-up. A 10% solution of
dishwasher detergent and water is recommended for
both sides of the coil. A thorough water rinse should
follow.
UV based anti-bacterial systems may damage
coated air coils.
Notice!
Installation Note - Ducted Return: Many
horizontal WSHPs are installed in a return air ceiling
plenum application (above ceiling). Vertical WSHPs are
commonly installed in a mechanical room with free return
(e.g. louvered door). Therefore, fi lter rails are the industry
standard and are included on ClimateMaster commercial
heat pumps for the purposes of holding the fi lter only.
For ducted return applications, the fi lter rail must be
removed and replaced with a duct fl ange or fi lter rack.
Canvas or fl exible connectors should also be used to
minimize vibration between the unit and ductwork.
Unit Hanger Kits
(included)
Insulated supply duct with
at least on 90 deg. elbow
to reduce air noise
Suppy Air
Unit Power
Disconnect
Ball valve with optional
integral P/T plug
Unit Power
Power Wiring
Thermostat
Wiring
Stainless Steel
Braid Hose with
Integral “J” Swivel
3/8” [10mm] thread rods
(by others)
Building
Water out
Water in
Loop