TECHNICAL MANUAL  

CVM 2 

C 5001 CV/04-99 GB

 

  

19

 

 

26 

ANTIFREEZE ALARM SET 

p.62

p.63 

30     
°C/10 

27 

ANTIFREEZE HYSTERESIS 

0

126 

40     
°C/10 

28 

ANTIFREEZE RESET TYPE 

0=AUTOMATIC     
1=MANUAL 

1    flag 

29 

ANTIFREEZE ALARM BY-PASS CONFIGURATION 
(E05/E25) FOR CIRCUIT 1 AND 2 

0=NEVER            
1=HEAT         
2=COOL         
3=ALWAYS 

1     num. 

31 

ANTIFREEZE BY-PASS TIME 

0

255 

30     sec 

32 

ANTIFREEZE HEATER START SET POINT  

-280

500 

30     
°C/10 

33 

ANTIFREEZE HEATER START HYSTERESIS 

0

126 

40     
°C/10 

 

38 

FAN MOTORS PHASE ANGLE VALUE 

0

126 

5     num. 

 

39 

WATER PUMP OPERATING MODE 

0=NOT PRESENT 
1=CONTINUOUS   
2=ON REQUEST BY 
THERMO-
REGULATOR 

1     num. 

40 

COMPRESSOR START DELAY AFTER PUMP 
START 

0

126 

60     sec 

41 

PUMP SHUTDOWN DELAY AFTER 
COMPRESSOR SHUTDOWN 

0

126 

60     sec 

42 

DIFFERENTIAL PRESSURE SWITCH AND 
EXTERNAL FLOW SWITCH ALARM BY-PASS 
(E41) UPON PUMP START 

0

126 

30     sec 

43 

DIFFERENTIAL PRESSURE SWITCH AND 
EXTERNAL FLOW SWITCH ALARM RESET BY-
PASS (E41) 

0

126 

10     sec 

 

44 

CO 

TYPE OF  RESET OF COMPRESSOR THERMAL 
PROTECTION ALARM (E03/E23) 

0=AUTOMATIC 
1=MANUAL 

1     flag 

45 

CI 

TYPE OF  RESET OF FAN THERMAL 
PROTECTION ALARM  (E04/E24) 

0=AUTOMATIC 
1=MANUAL 

1     flag 

46 

CO 

COMPRESSOR THERMAL PROTECTION ALARM 
BY-PASS TIME (E03/E23) 

0

126 

1     sec 

 

47 

TEMPERATURE UNIT OF MEASUREMENT 

0=CELSIUS  
1=FAHRENHEIT 

0     flag 

48 

0

126 

20     
°C/10 

 

49 

SAFETY TIME BETWEEN COMPRESSOR START 
AND SHUTDOWN 

0

126 

6     sec 
x10 

50 

SAFETY TIME BETWEEN 1

st

 AND 2

nd

 

COMPRESSOR START 

0

126 

36     sec 
x10 

Summary of Contents for CVM 2

Page 1: ...UPPLY 8 2 SETUP 8 2 1 ACCESS TO PROGRAMMING 8 3 SOFTWARE 9 3 1 DESCRIPTION OF USER INTERFACE 9 3 2 UNIT STARTUP 9 3 3 UNIT SHUTDOWN 10 3 4 ALARMS 10 3 4 1 Circuit and or compressor alarms 10 3 4 2 Gen...

Page 2: ...ated inside the electrical panel and of a keyboard Enclosures fig 1 The boards for the continuous adjustment of the fan speed are connected to the main board The keyboard communicates with the main bo...

Page 3: ...HNICAL MANUAL CVM 2 C 5001 CV 04 99 GB 3 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 Figure 1 1 MAIN BO...

Page 4: ...r temperature Temperature C 55 50 40 30 20 Resistance 485 510 562 617 677 Temperature C 10 0 10 20 25 Resistance 740 807 877 951 990 Temperature C 30 40 50 60 70 Resistance 1029 1111 1196 1286 1378 Te...

Page 5: ...0 15 5 Current mA 11 43 10 69 10 96 11 23 11 49 11 76 12 03 12 30 Pressure Bar 16 0 16 5 17 0 17 5 18 0 18 5 19 0 19 5 Current mA 12 56 12 83 13 10 13 37 13 63 13 90 14 17 14 44 Pressure Bar 20 0 20 5...

Page 6: ...Circuit 1 compressor thermal protection 14 AT6 Circuit 2 compressor thermal protection 19 AT7 Circuit 1 fans thermal protection 13 AT8 Circuit 2 fans thermal protection 20 AT9 Water differential press...

Page 7: ...1 1 KEYBOARD CONNECTION 1 7 Remote keyboard Figure 1 2 REMOTE KEYBOARD CONNECTION NB The supplementary transformer is the 230 12 Vac transformer supplied with the remote keyboard kit The maximum leng...

Page 8: ...gh the parameter list using the arrow up and arrow down keys to visualise the required parameter Press the SET key the value of the parameter on the left hand side of the display will start flashing M...

Page 9: ...and stand by condition required by the timer Then they become steady indicating operational readiness first of COMPRESSOR 1 and then of COMPRESSOR 2 If the unit is a HEAT PUMP the HEATING LED comes o...

Page 10: ...ssor alarms are visualised with the corresponding flashing code on the DISPLAY while the ALARM LED comes on The related compressor is simultaneously shut down Alarm reset Press the ON OFF RESET key th...

Page 11: ...l protection Manual Possible compressor motor malfunction E04 Circuit 1 fan thermal protection Manual Possible electric fan motor malfunction E05 Circuit 1 antifreeze Manual Check the water flow rate...

Page 12: ...to the evaporator Check the operation of the water pump Verify if cold set point is correct parameters 2 58 59 E26 ST3 probe malfunction Automatic Check the connections to board terminals 5 and 6 Pro...

Page 13: ...urs Operating hours since last operating hours reset 03 Circuit 1 fans 01 operating 02 off for defrosting 06 fans off 04 Circuit 1 defrosting not present 01 defrosting 02 compressor 1 safety count 03...

Page 14: ...resent value in C 10 ERR probe error 44 Condensing water inlet temperature reading for unit with reversing cycle on water side ST5 or condensing pressure reading for unit with fans speed regulation SP...

Page 15: ...et point 12 C 4 Chiller differential 1 C 48 t 2 C NB regulation is made based on the temperature reading at the evaporator inlet 6 2 Hot water regulation To modify the working set point of the unit in...

Page 16: ...hiller 1 Water water chiller 3 Water air heat pump 5 Water water heat pump with reversing cycle on liquid side Table 7 1 UNIT TYPE 2 M COLD SET POINT COOLING p 58 p 59 120 C 10 3 M WARM SET POINT HEAT...

Page 17: ...11 M CIRCUIT No 2 FAN OPERATING MODE 0 MODULATING OUTPUT 1 ON OFF 2 DISABLED 0 num 12 M MODULATING OUTPUT LOWER LIMIT 0 100 30 13 M MODULATING OUTPUT UPPER LIMIT 0 100 100 14 M SUMMER CUT OFF SET POIN...

Page 18: ...23 M MAXIMUM DEFROST TIME 0 126 5 min 24 M DELAY BETWEEN FIRST CIRCUIT END OF DEFROST AND SECOND CIRCUIT START DEFROST 0 126 2 min 25 M FORCED VENTILATION PRESSURE DURING DEFROST 0 30 16 Bar CHILLER...

Page 19: ...SOR START DELAY AFTER PUMP START 0 126 60 sec 41 M PUMP SHUTDOWN DELAY AFTER COMPRESSOR SHUTDOWN 0 126 60 sec 42 M DIFFERENTIAL PRESSURE SWITCH AND EXTERNAL FLOW SWITCH ALARM BY PASS E41 UPON PUMP STA...

Page 20: ...2 CIRCUIT CONFIGURATION 58 M SUMMER SET POINT LOWER LIMIT CHILLER 20 p 2 10 C 59 M SUMMER SET POINT UPPER LIMIT CHILLER p 2 50 20 C 60 M WINTER SET POINT LOWER LIMIT HEAT PUMP 10 p 3 30 C 61 M WINTER...

Page 21: ...P5 PROBE OFFSET 100 100 Bar 10 83 M SP6 PROBE OFFSET 100 100 Bar 10 84 CI DEFROST CYCLES 0 NOT ENABLED 1 ENABLED 1 flag 85 CI ANTIFREEZE HEATER 0 ABSENT 1 PRESENT flag 86 CI OPERATION OF ANTIFREEZE HE...

Page 22: ...0 E p 68 2 2 PRESENT ONLY FOR ON OFF Table 7 5 REMOTE CONTROL CONFIGURATION WARNING If the unit is switched off using the keyboard s ON OFF key the antifreeze resistance control will also go off This...

Page 23: ...TECHNICAL MANUAL CVM 2 C 5001 CV 04 99 GB 23 8 Enclosures...

Reviews: