background image

1

EMD-1ZBS Electricity Power Reader 

Introduction

 

The  Energy  Meter  is  a  ZigBee  Electricity  Power  reader  designed  to  be  used  with  a  digital  watt  hour  meter 
supporting LED pulse output port. The E-meter reads the LED pulse from the watt hour meter and transmits the 
data to ZigBee network coordinator. 
The Energy Meter utilizes ZigBee technology for wireless signal transmission. ZigBee is a wireless communication 
protocol  that  is  reliable,  has  low  power  consumption  and  has  high  transmission  efficiency.  Based  on  the 
IEEE802.15.4 standard, ZigBee allows a large amount of devices to be included in a network and coordinated for 
data exchange and signal transmission. 
The Energy Meter serves as an end device in the ZigBee network. It can be included in the ZigBee network to 
transmit signal upon activation, but cannot permit any other ZigBee device to join the network through the Energy 
Meter. 

Parts Identification 

1. LED indicator

The LED indicator lights up in the following conditions:

- Flashes quickly: 

              The Energy Meter received LED signal. 

- Flashes once: 

The Energy Meter is reset. 

- Flashes twice: 

The Energy Meter has successfully joined a ZigBee network. 

- Flashes every 20 minutes 

The Energy Meter has lost connection to current ZigBee network 

2. Mounting Holes
3. Battery compartment Cover

Remove the cover to insert 2 Alkaline AA 1.5V batteries to power up the
Energy Meter.

4. LED Sensor Jack

Plug the Sensor into this jack to receive LED signal from the watt hour
meter.

5. Function Button

- Press the button once to transmit supervision signal. 
- Press and hold the button for 10 seconds then release to reset the 

Power Meter. 

6. IR Sensor

Attach the IR sensor to the watt hour meter, and plug into the IR sensor
Jack to read data from the watt hour meter.

Features 

Battery and Low Battery Detection

The  Energy  Meter  uses  2  Alkaline  1.5V  batteries  as  its  power  source,  It  feature  Low  Battery  Detection 
function. When the battery voltage is low, the Energy Meter will transmit Low Battery signal to notify ZigBee 
network coordinator.   
When changing battery, after removing the old batteries, press the function button a couple times to fully 
discharge before inserting new batteries 

Supervision

T

he Energy Meter will transmit a supervision signal to report its condition regularly according to user setting.

The factory default interval is 30 minutes. The user can also press the Function Button once to transmit a
supervision signal manually.