Power supply cables section / power bars
Size
90.4
100.4
110.4
120.4
140.4
160.4
Min. cable section Cu (mm²)
1x95
1x95
1x150
1x150
1x150
1x240
Max. cable section Cu (mm²)
1x185
1x185
1x240
1x240
1x240
1x240
Min. bar Cu section (mm²)
-
-
-
-
-
-
Max. bar Cu width (mm)
32
32
32
32
32
40
Tightening torque (Nm)
20
20
20
20
20
20
6.
6
Remote ON-OFF
Do not perform short On Off
c
ycles
Do not use the remote On Off with the
r
moregulation function.
A B
A
B
Y E S
N O !
A
B
A
B
20