7.14 Climatic TExt
Menu accessible only after having entered the password.
Access reserved only to specifically t
r
ained personnel.
The parameter modific
a
tion can cause irreversible damages.
The setpoint defined
b
y the temperature curve is shown at status S0052: ActualUtSetp
Only if P0036: EnCompExt ≠ 0
Path: Main Menu / Unit parameters / TExt Correction confi
Example
P0612
P0610
P0613
-5
5
10
15
5
10
15
25
30
P0606
P0609
P0607
18
22 24 26 28 30 32 34
2
4
6
8
10
12
14
16
34
0
25
30
20
0
20
T ext.
T ext.
setpoint
setpoint
Cooling
P0608
Heating
P0611
S0052
S0052
20
Step Display
Action
Menu/Variable
Keys
Notes
1
Press 3 sec.
2
Password
Set
Password
3
Press
4
Main menu
Select
Unit parameters
5
Unit parameters
Select
Climatic TExt
6
Climatic TExt (pwd)
Select
Parameter
7
Set
8
Confirm
9
Press 3 sec.
10
Select
Local connections
Path: Main Menu / Unit parameters / TExt Correction config
Parameters
Short description
description
P0606
CSptLow
setpoint temperature value when the air temperature value is AirAtSptLowC
P0607
AirAtSetPointLowC
external air temperature value where the calculated setpoint takes on the value given by CSptLow
P0608
CSptHigh
setpoint temperature value when the air temperature value is AirAtSptHigC
P0609
AirAtSetPointHighC
external air temperature value where the calculated setpoint takes on the value given by CSptHigh
P0610
HSptLow
setpoint temperature value when the air temperature value is AirAtSptLowH
P0611
AirAtSptLowH
external air temperature value where the calculated setpoint takes on the value given by HSptLow
P0612
HSptHigh
setpoint temperature value when the air temperature value is AirAtSptHigH
P0613
AirAtSptHigH
external air temperature value where the calculated setpoint takes on the value given by HSptHigh
P0606 / P0609: Coooling
P0610 / P0613: Heating
29
Summary of Contents for MSE-XSC3 100.4
Page 1: ...MSE XSC3 90 4 160 4 Installation and operating manual...
Page 3: ...Index of contents 1 4 2 6 3 8 4 10 5 14 6 18 7 26 8 35 9 47 10 52 11 53 12 54 57 3...
Page 19: ...Connections performed by the Customer 19...
Page 50: ...9 15 Compressor replacement 50...
Page 51: ...9 16 Exchanger replacement 51...