7.15 Water reset
Menu accessible only after having entered the password.
Access reserved only to specifically t
r
ained personnel.
The parameter modific
a
tion can cause irreversible damages.
The water reset correc
tion aff
ects the setpoint defined y the Climate curve TExt (actual setpoint).
The setpoint is shown at status S0052: ActualUtSetp
Only if P0003: En WaterReset ≠ 0
Path: Main menu / Unit parameters / Water reset confi
Step Display
Action
Menu/Variable
Keys
Notes
1
Press 3 sec.
2
Password
Set
Password
3
Press
4
Main menu
Select
Unit parameters
5
Unit parameters
Select
Water reset
6
Water reset
Select
Parameter
7
Set
8
Confirm
9
Press 3 sec.
10
Select
Local connections
Path: Main Menu / Unit parameters / Water reset
Parameters
Short description
description
P0616
MaxCWRC
Maximum correction to be applied to the setpoint Cooling
P0617
SWRMaxC
Value of the WR control signal corresponding to the correction of the set Cool equal to P0616
P0618
SWRMinC
Value of the WR control signal corresponding to the correction of the set COOL equal to 0
P0615
MaxCWRH
Maximum correction to be applied to the setpoint Heating
P0619
SWRMaxH
Value of the WR control signal corresponding to the correction of the set Heating equal to P0615
P0620
SWRMinH
Value of the WR control signal corresponding to the correction of the set Heating equal to 0
P0616 / P0618: Cooling
P0615, P0619, P0620: Heating
30
Summary of Contents for MSE-XSC3 100.4
Page 1: ...MSE XSC3 90 4 160 4 Installation and operating manual...
Page 3: ...Index of contents 1 4 2 6 3 8 4 10 5 14 6 18 7 26 8 35 9 47 10 52 11 53 12 54 57 3...
Page 19: ...Connections performed by the Customer 19...
Page 50: ...9 15 Compressor replacement 50...
Page 51: ...9 16 Exchanger replacement 51...