background image

 

M0G940E8-00 04/07/08 

pag 

15 

 

WATER CONNECTIONS

 

 

GENERAL 

Piping must be designed with the least possible number of 
bends and head variations. If the pressure chute of the 
installation is above the useful prevalence of the pump, the 
water delivery capacity is reduced as well as, as a 
consequence, the thermal exchange and the yield.  

INTERCEPTING VALVES 

Install on the input and output of the user parts 
(exchangers, coils, humidifiers, etc) So that it will be 
possible to carry out all the service operations and possible 
substitutions without emptying the installation. 

PRESSURE AND TEMPERATURE INDICATOR 

Install on the input and output of the user parts 
(exchangers, coils, humidifiers, etc) So that it will be 
possible to carry out all the service operations. 

AUTOMATIC OR MANUAL ESCAPE VALVES 

Install the highest points of tubes in a way that the air can 
escape form the circuit.  

BLEEDING COCK 

Install them at the lowest points of the circuit, so as to allow 
emptying. 

LEAKAGE TESTS 

Before performing the insulation of the tubes, carry out a 
leakage test. 

TUBE INSULATION  

All tubes of water must be insulated so that to avoid the 
formation of condensation and thermal dispersions along 
the tubes themselves. Verify that the insulation is the 
vapour coil type. The connections for the air escape and for 
the emptying must be out of the insulating thickness to 
assure the accessibilità. 

CONNECTIONS SUPPORTS 

The weight of the hydraulic connections must be supported 
in the exterior of the unit so as not to stress the connections 
of user devices (exchangers, coils, humidifiers, etc ) . 

ANTI-VIBRATION DEVICES 

In case of units with anti-vibration devices, it is necessary to 
assemble elastic joints, even on water connections. 

RISK OF FREEZE 

If the unit and the relevant water connections are subject to 
temperatures near 0°C:  

• 

mix the water of the system with glycol 

• 

protect the tubes with heating cables under the tubes 
insulation 

• 

empty the system by verifying that: 

no taps are closed so they can not trap the water, 
even after emptying 

there are no low points where the water can 
stagnate even after emptying; blow if necessary 

INTALLATION EMPTYING  

The refilling of the water present in the installation increase 
the oxidation phenomena and lime deposits.  
If necessary empty only the interested system section and 
anyway empty or refill the installation if necessary .  

EXPANSION TANK 

The installation must be kept at the right pressure by both 
an expansion tank and a combined valve of pressure 
reduction and discharge; if the components are present on 
the unit, they must be installed on the installation. The 
expansion tank must be dimensioned in function of the 
water in the installation. 

 
 
 

EXCHANGER USE SIDE 

 

FILTER 

It is very important for the water to be free of impurities. If it 
is not, the efficiency of thermal exchange is diminished. In 
worst cases, the exchanger can be irreparably damaged. If 
the filter is not present on the machine, it must be 
immediately installed upstream from the unit, in a position 
which can be easily reached for cleaning. 
The filter mesh must be :  

• 

< 1 mm unit with 1 compressor 

• 

< 1.5 mm multicompressor unit. 

FLOW SWITCH 

The flow switch must be present as a component of the 
system, so as to ensure shutdown of the unit if water is not 
circulating. It must be installed in a straight tract of the 
tubes, not near the elbows, which can generate harmful 
turbulence  

UNFREEZABLE LIQUIDS 

If the unit is used when the water temperature is lower than 
+ 4°C, avoid the formation of ice by using unfreezable 
liquids (ex. Ethilenic Glycol) in the necessary percentage. 
The use must also be determined for ambient temperatures 
near 0°C . 

ANTIFREEZE RESISTANCES  

If the unit is equipped with antifreeze resistances on the 
exchanger side (standard or optional according to the 
models), verify that they are electrically fed during periods 
that the machine is stopped (night, weekends, long stops) 

WASHING THE SYSTEM 

Carefully wash the system by using clean water and 
discharge it before connecting the unit. 

 

Summary of Contents for WSAN-XPR 21

Page 1: ...WSAN XPR 21 31 41 51 AIR TO WATER HEAT PUMP FOR OUTDOOR INSTALLATION Installation and Use Manual M0G940E8 00 04 07 08...

Page 2: ......

Page 3: ...LIMINARY CHECKS 32 REFRIGERANT SYSTEM 32 WATER SYSTEM 32 ELECTRICAL SYSTEM 32 VERIFy tensions absorptions 33 UNIT EQUIPPED WITH SCROLL COMPRESSORS 33 REMOTE INPUT CONFIGURATIONS 33 SETTING THE SET POI...

Page 4: ...AL NUMBER This provides unique identification of the machine It makes it possible to trace the specific features of the unit and to identify the components installed in it Without this number it is no...

Page 5: ...2 1 3 4 5 6 WINTER the cooling cycle makes it possible to absorb energy heat at low temperature from the external environment and to transfer it to the area to be heated 1 The compressor compresses t...

Page 6: ...aintaining the system at a safety temperature in WINTER MAINTENANCE function Put the unit in OFF parameter 45 must be 1 yellow led is flashing Minimize the consumptions maintaining the system at a saf...

Page 7: ...g Control parameter parametro 43 Modify the water temp in MAINTENANCE cooling Control parameter 42 Only by SERVICE keypad A L A R M S T A T U S S E T COMMON CAUSES OF SHUTDOWN 1 coils dirty clogged by...

Page 8: ...does not respect the instructions given in this manual will cause the warranty to lapse INTENDED USE The unit must only be used for the specific purpose it was designed The unit is designed to cool h...

Page 9: ...zed entry GENERAL RISKS A smell of burning smoke or other indications of serious irregularity could signal the onset of situations liable to cause damage to persons or property or to the unit itself I...

Page 10: ...er Chart No FRIG 8 Product R 410A Identification of the supplier See heading or bottom of page No of emergency telephone See heading or bottom of page 02 Composition information on ingredients Substan...

Page 11: ...ed from the driver compartment Verify that the driver is informed on the potential risk of the load and that he knows what to do in case of an accident or emergency Before starting the transport verif...

Page 12: ...ressure of the circuits can assume values which activate the safety valves HANDLING The operation of handling the unit must be carried out respecting the instructions of the safety norms in force Legi...

Page 13: ...nt and can only be placed there The anti vibration devices must therefore be placed in accordance with the instructions provided with them and with the dimensional drawings in which the support points...

Page 14: ...ximum depth that snowfall might reach A 2 A Tree 1 3 2 1 elastic joint 2 floating floor 3 soundproofing Consider clearances and direction of expelled air Keep the coil clean Avoid zones with leaves di...

Page 15: ...tubes insulation empty the system by verifying that o no taps are closed so they can not trap the water even after emptying o there are no low points where the water can stagnate even after emptying b...

Page 16: ...ys ON OFF sanitary H2O 3 sanitary boiler 4 fancoil 5 3 ways radiant panels 6 radiant pump 7 radiants 8 pump for more details see the ELECTRICAL DATA section and the SYSTEM SCHEMA WITH ACCESSORIES at p...

Page 17: ...ing to the characteristics of the protections used SIGNALS DATA LINES Do not overpass the maximum power allowed which varies according to the type of signal Lay the cables far from power cables or cab...

Page 18: ...TERMINAL Permits setting the unit function modes cooling heating ECO and to display the alarms ELECTRIC REFRIGERATOR WATER This is standard on certain types of unit L N 91 92 STA TU S SET ALA RM 2 1 R...

Page 19: ...tic hot water boiler page 30 1 ON OFF FROM REMOTE CONTROL Generally the unit is delivered with bridged terminals if the control is not used bridge terminals 2 CHANGING FROM SUMMER TO WINTER USING THE...

Page 20: ...s disabled due to an external temp lower than par 180 1 1 MAIN ADJUSTMENT UNIT IN HEATING MODE in heat pump mode the compressor is disabled 2 1 POWER LIMITATION ACCORDING TO EXTERNAL TEMPERATURE the f...

Page 21: ...econd set point Refer to the wiring diagram to identify the corresponding terminals PLUG IN module 26 25 24 23 22 30 29 28 27 CN3 1 3 5 7 9 11 2 4 6 8 10 12 par Description Meaning value 49 Comando2 S...

Page 22: ...HEATING LIMIT avoids dew overheating ATTENTION to prevent dew in summer or superheating in winter it is very important to fit an external device and interface it with the unit that in case of signall...

Page 23: ...orresponding signal of the summer MIN correction 4 140 PlugInEn Enables PLUG IN presence 1 YES 0 NO SET POINT CURVE IN COOLING SET POINT CURVE IN HEATING mA P 23 P 24 COMP MAX P22 COMP 0 SET POINT mA...

Page 24: ...conductors twisted and shielded Section of conductor 0 22mm 2 0 35mm 2 Nominal capacity between conductors 50 pF m nominal impedance 120 Recommended cable BELDEN 3105 A TYPE OF NETWORK The serial lin...

Page 25: ...M0G940E8 00 04 07 08 pag 25...

Page 26: ...DRAULIC DIAGRAM WSAN XPR DOMESTIC HOT WATER RADIANT PANELS UR BT1 R E WSAN XPR RS 485 AP5 GN D AP5 ACS BT2 DOMESTIC HOT WATER KIT FLEXIBLE PIPE KIT PEE20016 1 x BT1 R E 1 x 1 x 1 x ACS 1 x RS 485 AP5...

Page 27: ...G940E8 00 04 07 08 pag 27 WIRING DIAGRAM BT2 92 91 90 88 87 XC UR BT1 R E GND RS485 1 3 6 2 83 61 87 XC ACS 400 3 50 N N L3 L2 L1 26 L H GND XC 21 81 RS 485 AP5 GND RS485 61 86 ACS ACS Hydraulic diagr...

Page 28: ...HYDRAULIC DIAGRAM WSAN XPR DOMESTIC HOT WATER FAN COILS BT1 R E UR RS 485 AP5 GN D AP5 WSAN XPR ACS BT2 DOMESTIC HOT WATER KIT FLEXIBLE PIPE KIT PEE20016 1 x BT1 R E 1 x 1 x 1 x ACS 1 x RS 485 AP5 GN...

Page 29: ...G940E8 00 04 07 08 pag 29 WIRING DIAGRAM UR BT1 R E GND RS485 1 3 6 2 61 87 81 XC ACS RS485 400 3 50 N N L3 L2 L1 83 L H GND XC 21 25 92 91 90 88 87 XC RS 485 AP5 GND 61 86 ACS BT2 ACS Hydraulic diagr...

Page 30: ...6 25 24 23 22 30 29 28 27 ON OFF BT2 DOMESTIC HOT WATER KIT HYDRAULIC CIRCUIT BREAKER HYDRAULIC CIRCUIT BREAKER PEE20016 1 x BT1 R E 1 x 1 x 1 x ACS 1 x RS 485 AP5 GND KSAX 1 x KTFL1X 2 x BOILER MANAG...

Page 31: ...P5 GND ON OFF 25 21 26 83 84 81 87 61 UR GND RS485 RS485 3 2 6 1 SMR TS 6 2 1 3 7 F N PE 61 6 BT5 XC2 XT3 29 61 55 XT3 29 34 XT3 F PE N 85 61 86 ACS XC3 8 9 SDCV PE 61 6 7 81 5 4 27 28 30 XT3 25 23 81...

Page 32: ...osition Check that there is no air in the circuit If required bleed it using the vent valves in the system When using antifreeze solutions make sure the glycol percentage is suitable for the type of u...

Page 33: ...ated ON OFF etc as given in the instructions in the ELECTRIC WIRING chapter SETTING THE SET POINT Check if it is necessary to modify the set points shown in the CONTROL chapter EVAPORATOR WATER FLOW R...

Page 34: ...CAL CONNECTIONS paragraph CHARACTERISTICS THERMOREGULATION The thermoregulation is based on the OUTLET temperature The unit is dimensioned for a determined TOTAL HEAD between input and output water te...

Page 35: ...ating with low external temperatures so with a reduced charge is possible to obtain the internal comfort also with set point higher than standard obtaining an higher energetic efficiency CORRECTION AC...

Page 36: ...INTER the speed increases according to the decrease of the external tempe SET POINT SUMMER WINTER The thermoregulator manages two set points SUMMER set point for cooling parameter 32 WINTER set point...

Page 37: ...es that manage sanitary hot water production the status is displayed with the WINTER and SUMMER operation LEDs WINTER SUMMER ON FLASHING ON OFF The ON OFF control from the keyboard allows activating o...

Page 38: ...System charged with water Radiant panel water probe CCMP VENT Antifreeze alarm Coil flow probe HP1 Pre Alarm Antifreeze PREAlarm External probe BP1 Pre Alarm Pump alarm Pressure 1 probe C1 PREAlarm W...

Page 39: ...nt 5 7 C 33 Winter Set Point 41 2 C 42 Summer Set Point Maintenance 20 C 43 Winter Set Point Maintenance 30 C 44 Enables Summer Maintenance 0 num 45 Enables Winter Maintenance 0 num 77 Antifreeze heat...

Page 40: ...12 Coil temperature C 13 Condensing pressure Bar 14 Fan Valve 1 percentage 0 100 15 Heater output temperature 18 Water Reset signal value 4 20 mA 19 Outdoor temperature C 20 Outdoor Humidity 0 100 21...

Page 41: ...E 00 Serial faulty comunicazione tastiera scheda base Auto E 1 Faulty or disconnected water inlet probe Auto E 2 Faulty or disconnected water outlet probe Auto E 3 Faulty or disconnected radiating pan...

Page 42: ...m the surface Using an air pressure gun clean the aluminum surface of the battery Be careful to direct the air in the opposite direction of the fan air movement Hold the gun parallel to the fins to av...

Page 43: ...s as well Refer to local actuation norms In Italy refer to the Ministerial Decree of 1 st December 2004 no 329 and following modifications which defines the performances to be executed the units of 1...

Page 44: ...15 8 25 57 20 8 35 71 25 8 44 22 30 8 51 59 35 8 58 09 40 8 63 92 1 0 37 03 6 0 4 10 11 0 13 40 16 0 26 01 21 0 36 08 26 0 44 53 31 0 51 86 36 0 58 34 41 0 64 14 1 2 34 84 6 2 3 24 11 2 13 97 16 2 26...

Page 45: ...in cooling 1 low air temperature see operating limits 2 low water temperature see operating limits 3 insufficient water flow to the exchanger high thermal difference between input and output 4 not CON...

Page 46: ...air temperature see operating limits 2 high water temperature see operating limits 3 insufficient water flow to the exchanger high thermal difference between input and output 4 not CONSTANT flow for...

Page 47: ...must be stored in special containers When recovering the substances present in the unit all measures must be taken to avoid damaging persons and things and polluting the surrounding area Awaiting dism...

Page 48: ...M0G940E8 00 04 07 08 pag 48...

Page 49: ...M0G940E8 00 04 07 08 pag 49 TECHNICAL DATA...

Page 50: ...onsidered In the event of multiple units the functional clearances must be doubled Size 21 M mm 349 N mm 161 O mm 176 P mm 160 Length mm 800 Depth mm 300 Height mm 930 W1 kg 15 W2 kg 32 W3 kg 14 W4 kg...

Page 51: ...nces for operation and maintenance The following sketch describes the minimum clearances to be considered In the event of multiple units the functional clearances must be doubled Size 31 41 M mm 334 3...

Page 52: ...ered In the event of multiple units the functional clearances must be doubled Size 51 M mm 343 N mm 167 O mm 144 P mm 192 Length mm 800 Depth mm 300 Height mm 1370 W1 kg 19 W2 kg 39 W3 kg 26 W4 kg 51...

Page 53: ...1 kPa 64 85 70 85 EXTERNAL SECTION FANS Type of fans 8 AX AX AX AX Number of fans Nr 2 2 2 3 Standard air flow 1 l s 1014 1030 1270 1764 Installed unit power kW 0 09 0 09 0 115 0 12 CONNECTIONS Water...

Page 54: ...5 C 1 kPa 46 70 41 69 EXTERNAL SECTION FANS Type of fans 9 AX AX AX AX Number of fans Nr 2 2 2 3 Standard air flow 1 l s 1014 1030 1270 1764 Installed unit power kW 0 09 0 09 0 115 0 12 CONNECTIONS Wa...

Page 55: ...ns 8 AX AX AX AX Number of fans Nr 2 2 2 3 Standard air flow 1 l s 1014 1030 1270 1764 Installed unit power kW 0 09 0 09 0 115 0 12 CONNECTIONS Water fittings 1 GAS 1 GAS 1 GAS 1 GAS HYDRAULIC CIRCUIT...

Page 56: ...EXTERNAL SECTION FANS Type of fans 9 AX AX AX AX Number of fans Nr 2 2 2 3 Standard air flow 1 l s 1014 1030 1270 1764 Installed unit power kW 0 09 0 09 0 115 0 12 CONNECTIONS Water fittings 1 GAS 1 G...

Page 57: ...to unit operating with fans at max flow rate It follows an energy efficiency increase but also a sound pressure increase of about 2 3 dB A 3 external exchanger air intake 30 C Maximum exchanger inlet...

Page 58: ...n the external exchanger having clean plates fouling factor 1 For different fouling factor values multiply the performance by the coefficients shown in the table F1 Cooling capacity correction factors...

Page 59: ......

Page 60: ...24 info clivet nl CLIVET TFAIRSYSTEMS P LTD Malur INDIA Tel 91 8151 232683 5 Fax 91 8151 232684 info clivettfa com CLIVET SPA BUREAUDE LIAISON EN FRANCE Verrier s le Buisson FRANCE Tel 33 0 1 69 20 25...

Reviews: