M0G940E8-00 04/07/08
pag
16
DIAGRAM OF RECOMMENDED USE SIDE CONNECTION
Depending on the type of machine and the selected setup, some components may be integrated into the unit.
P
9
11
14
8
F
2
3
5
12
7
6
4
8
1
10
13
P
7
1. Charged system pressure switch
2. vent
3. pump
4. expansion
tank
5. safety
valve
6. flow
switch
7. pressure switch / thermometer
8. filter
9. filling
valve
10. antivibration joints
11. user side exchanger
12. Differential pressure switch
13. Discharge cock
14. inertial storage tank
The accumulation tank is necessary in the event of the following:
•
the water in the system is very low
•
the unit will not be used in a private house (in an industrial process or other)
USE SCHEMA
8
1
2
3
4
5
6
7
8
1. Heating
integration
2. 3-ways ON-OFF sanitary H2O
3. sanitary
boiler
4. fancoil
5. 3-ways radiant panels
6. radiant
pump
7. radiants
8. pump
for more details see the ELECTRICAL DATA section and
the SYSTEM SCHEMA WITH ACCESSORIES at page
26
WINTER CONDENSATION
When a heat pump is running it produces a considerable
amount of water due to the defrosting cycles of the external
coil.
The condensation must be eliminated in a manner to avoid
wetting pedestrian areas.
With extensive very cold outdoor temperatures,
condensation could freeze and block the flow, causing a
slow build-up of ice;
therefore special attention must be paid to eliminating
condensation, raising the unit off the ground and evaluating
whether antifreeze elements should be installed
For units with condensation trays, refer to the dimensional
diagrams to calculate the condensation discharge.
For units without condensation tray, evaluate the suitability
of placing a tray beneath the unit base.