M0G940E8-00 04/07/08
pag
40
VISIBLE STATUS FROM REMOTE KEYBOARD OR SERVICE KEYBOARD
INDEX DESCRIPTION
VALUE
1
Current Set Point
°C
2
Temperature drop in degrees centigrade given by the compressor including
compensations, if any
°C
3
Resource activation timer
When this value reaches the value fixed at the 4 status, the thermal regulator will compare
the input temperature with the set point and will activate the resources, if necessary
Secondi
4
Dynamic TimeScan relating to source activation
Secondi
5
Value in degrees of the external air compensation
°C
6
Value in degrees of the water reset signal compensation
°C
7
Value in degrees of the charge compensation
°C
9
Inlet temperature
°C
10
Outlet temperature
°C
11
Outlet temperature of radiant panel water
°C
12
Coil temperature
°C
13
Condensing pressure
Bar
14
Fan/Valve 1 percentage
0-100%
15
Heater output temperature
18
Water Reset signal value
4-20 mA
19
Outdoor temperature
°C
20
Outdoor Humidity
0-100%
21
Machine Clock - fed unit hours
Num
22
Working hours C1
Num
23
Pickups C1
Num
24
Radiant panel valve status (Out-2)
ON-OFF
25
Radiant panel valve status
%
26
Percentage pump
%
27
Integration heater status
ON-OFF
28
Radiant panel valve status (Out-1)
ON-OFF
29
Radiant Set Point
°C
30
Keypad software
EJ – t
31
Year of certification of the keyboard SW
2007
32
Month of certification of the keyboard SW
04
33
Day of certification of the keyboard SW
03
34
Base Software
EJ – b
35
Year of certification of the keyboard SW
2007
36
Month of certification of the keyboard SW
03
37
Day of certification of the keyboard SW
14
STATUS DISPLAY
1
AL
AR
M
STATUS
SET
push STATUS button
2
AL
AR
M
ST
AT
US
SE
T
Select status
3
AL
ARM
STATUS
SET
STATUS to esc
Summary of Contents for WSAN-XPR 21