M0G940E8-00 04/07/08
pag
56
Application: Unit for underfloor heating
Size
21 31 41 51
COOLING
Cooling capacity (23/18°C - 35°C)
1
kW
7,39
9,02
11,8
15
Compressor power input (23/18°C - 35°C)
1
kW
1,84
2,33
3,13
3,92
Total power input
2
kW
2
2,52
3,42
4,34
EER (23/18°C - 35°C) EUROVENT
3,7
3,58
3,46
3,46
EER (EN 14511:2004; 23/18°C - 35°C)
3,47
3,4
3,4
3,4
ESEER
4,3
4,3
4,45
3,95
HEATING
Heat output (30/35°C - 7 °C D.B. / 6°C W.B.)
4
kW
6,76
7,81
10,5
13,1
Compressor power input (30/35°C-7°C D.B. / 6°C W.B.)
4
kW
1,41
1,7
2,3
2,74
Total power input
2
kW
1,65
1,91
2,58
3,19
COP (30/35°C - 7 °C D.B. / 6°C W.B.) EUROVENT
5
4,1
4,09
4,07
4,12
COP (EN 14511:2004; 30/35°C - 7 °C D.B. / 6°C W.B.)
6
3,96
3,9
3,9
4,06
COMPRESSOR
Type of compressors
7
SCROLL
SCROLL
SCROLL
SCROLL
No. of Compressors
Nr
1
1
1
1
Std Capacity control steps
Nr
1
1
1
1
Oil charge (C1)
l
1,1
1,25
1,25
1,95
Refrigerant charge (C1)
kg
2,9
5,2
5,4
5,7
Refrigerant circuits
Nr
1
1
1
1
INTERNAL EXCHANGER
Type of internal exchanger
8
PHE
PHE
PHE
PHE
Water flow rate (Internal Exchanger) (12/7°C - 35°C)
1
l/s
0,35
0,43
0,57
0,72
Useful pump discharge head (12/7°C - 35°C)
1
kPa
46
66
42
72
EXTERNAL SECTION FANS
Type of fans
9
AX
AX
AX
AX
Number of fans
Nr
2
2
2
3
Standard air flow
1
l/s
1014
1030
1270
1764
Installed unit power
kW
0,09
0,09
0,115
0,12
CONNECTIONS
Water fittings
1" GAS
1" GAS
1" GAS
1" GAS
HYDRAULIC CIRCUIT
Max water side pressure
kPa
550
550
550
550
Safety valve calibration
kPa
600
600
600
600
EXPANSION VESSEL
Expansion vessel capacity
l
1
2
2
2
No. of expansion vessels
Nr
1
1
1
1
POWER SUPPLY
Standard power supply
V
230/1/50
230/1/50
230/1/50
230/1/50
NOISE LEVELS
Sound pressure level (1 m)
dB(A)
55
55
56
59
DIMENSIONS
Length
mm
800
800
800
800
Depth
mm
300
300
300
300
Height
mm
930
1244
1244
1370
Packing volume
m
3
0,4
0,5
0,5
0,5
STANDARD UNIT WEIGHTS
Shipping weight
kg
91
108
113
137
Operating weight
kg
89
106
111
135
(1) data referred to the following conditions :
internal exchanger water = 23/18°C
external exchanger air intake 35°C
(2) Total input is obtained from compressor input +
fan input
(4) data referred to the following conditions :
water to internal exchanger 30/35°C
External air temperature : 7°C D.B./6.0°C W.B.
(5) COP calculated as the relationship between
heating capacity and total absorbed power.
(6) The indicated COP values were calculated in
compliance with the provisions of standard EN
14511:2004.
(7) SCROLL = scroll compressor
(8) PHE = plates
(9) AX = axial-flow fan
Summary of Contents for WSAN-XPR 21
Page 2: ......
Page 25: ...M0G940E8 00 04 07 08 pag 25...
Page 48: ...M0G940E8 00 04 07 08 pag 48...
Page 49: ...M0G940E8 00 04 07 08 pag 49 TECHNICAL DATA...
Page 59: ......