10
WSAN-XSC3 MF 90.4-240.4
M02M40N15-01
4 Water
connections
4.1 Water
quality
Water features
•
confirming to local regulations
•
total hardness < 14°fr
•
within the limits indicated by table
The water quality must be checked by qualified personnel.
Water with inadequate characteristics can cause:
•
pressure drop increase
•
reduces energy efficiency
•
increased corrosion potential
Acceptable water quality values:
SO
4
2-
HCO
3
-
/SO
4
2-
Total Hardness
Cl
-
PO
4
3-
< 100
> 1
4,5 ÷8,5
< 50
< 2,0
NH3
< 0,5
PH
7,5 ÷9,0
ppm
dH
ppm
ppm
ppm
Fe
3
+
Mn
++
CO
2
H
2
S
Temperature
< 0,5
< 0,05
< 50
< 50
< 65
Oxygen content
< 0,1
Free Chlorine
< 0,5
ppm
ppm
ppb
°C
ppm
ppm
ppm
Provide a water treatment system if values fall outside the limits.
The warranty does not cover damages caused by limestone formations, deposits and impurities from the water supply and / or failure from
failed system clearing to clean system.
4.2 Risk of freezing
If the unit or the relative water connections are subject to temperatures close to 0°C:
•
mix water with glycol, or
•
safeguard the pipes with heating cables placed under the insulation, or
•
empty the system in cases of long non-use
4.3 Anti-freeze
solution
The use of an anti-freeze solution results in an increase in pressure drop.
Make sure that the glycol type utilized is inhibited (not corrosive) and compatible with the water circuit components.
Do not use different glicol mixture (i.e. ethylene with propylene).
4.4 Water
flow-rate
The project water-flow must be:
•
inside the exchanger operating limits (see the TECHNICAL INFORMATION section)
•
guarantee, also with variable system conditions (for example in systems where some circuits are bypassed in particular situations).
Pumps externally installed is handled by the MULTIFUNCTION controller. Availability and operation of pumps has to be guaranteed in every
working condition.
For details see: Technical Bulletin, “Considerations on the installation” section
4.5 Minimum system water content
Minimum system water volumes are described within ‘General technical data’ section and they have to be satisfied to avoid continuous
compressor switching on and off.
With outdoor air low temperature applications or low medium requested loads, the minimum installation water volume is obtained doubling
the indicated value.
For details see: Technical Bulletin, “Considerations on the installation” section
Summary of Contents for WSAN-XSC3 MF 200.4
Page 20: ...20 WSAN XSC3 MF 90 4 240 4 M02M40N15 01 6 4 Configuration for 2 pipe system ...
Page 45: ...M02M40N15 01 WSAN XSC3 MF 90 4 240 4 45 8 17 Compressor replacement ...
Page 46: ...46 WSAN XSC3 MF 90 4 240 4 M02M40N15 01 8 18 Exchanger replacement ...
Page 47: ...M02M40N15 01 WSAN XSC3 MF 90 4 240 4 47 9 Accessories 9 1 Anti vibration mount support ...