40
WSAN-XSC3 MF 90.4-240.4
M02M40N15-01
R
EFRIGERANT CIRCUIT ALARMS
Num
Name
Description
Category
ff2005
Min overheating EEV1
Min Superheat value (user side)
Circuit 2
ff2006
Min overheating EEV2
Min Superheat value (source)
Circuit 2
fF2009
Low Pressure Alarm (DI)
Low pressure Alarm (DI)
Circuit 2
ff2010
Warning LP Cool
Low pressure Pre Alarm CoolingMode
Circuit 2
ff2011
Warning LP Heat
Low pressure Pre Alarm HeatingMode
Circuit 2
fF2012
Low pressure Alarm Heat (AI)
Low pressure Pre Alarm Heating Mode (AI)
Circuit 2
fF2013
High Pressure (DI)
High pressure Alarm (DI)
Circuit 2
ff2014
Warning High Pressure
High pressure Pre Alarm
Circuit 2
fF2015
High Pressure Alarm (AI)
High pressure Alarm (AI)
Circuit 2
ff2016
Max RC Warning
Maximum pressure Ratio Pre Alarm
Circuit 2
fF2017
Min RC Alarm
Minimum pressure Ratio Pre Alarm
Circuit 2
fF2018 Low
Pressure
Alarm
Cool(AI)
Low
Pressure Alarm Cooling Mode
Circuit 2
FF2019
Max RC Alarm
Maximum Pressure Radio
Circuit 2
FF2034
Vacuum Circuit
Vaacum Alarm
Circuit 2
FF2046
LimLp
Low pressure limit
Circuit 2
ff2047 DFRForced
Defrost
Forced
Circuit
2
ff2048
DFRWaterTLow
Low water temperature for defrost
Circuit 2
ff2049 DFRTimeMax
Defrost
Time
Circuit
2
HYDRAULIC CIRCUIT ALARMS
Num
Name
Description
Category
iI0002
Water pressure
User side low water pressure
GP Ut
iI0006
Flow switch utility side
User side low flow rate
GP Ut
II0007
Freeze alarm
User side Water Frost Protection
Centrale
ii0008 Pumps
antifreeze
alarm
Pump
activation Water Frost Protection
Centrale
II0009
Inconsistent deltaT across the exchanger
Water outlet temperature, discordant with the
current operation mode, user side
Centrale
II0042 Pressure
allarm
Freecooling
low water pressure
FCI Circuito 1
II0043 Freeze
alarm
Freecooling
water frost protection
FCI Circuito 1
ii0047
Flow switch allarm
Freecooling water low flow rate
FCI Circuito 1
iI0052
Recovery Low H2O Flow Recovery
water
low
flow rate
Recupero
iI0053
Recovery Low Pressure Plant
Recovery low water pressure
Recupero
iI1017
Source Low Pressure Plant
Source low water pressure
Sorgente 1
iI1020
Source Low H2O Flow
Source side low water flow
Sorgente 1
II1021
Source H2O Freeze Alarm
Source side water frost protection
Sorgente 1
iI2017
Source Low Pressure Plant
Source low water pressure
Sorgente 2
iI2020
Source Low H2O Flow
Source side low water flow
Sorgente 2
II2021
Source H2O Freeze Alarm
Source side water frost protection
Sorgente 2
Summary of Contents for WSAN-XSC3 MF 200.4
Page 20: ...20 WSAN XSC3 MF 90 4 240 4 M02M40N15 01 6 4 Configuration for 2 pipe system ...
Page 45: ...M02M40N15 01 WSAN XSC3 MF 90 4 240 4 45 8 17 Compressor replacement ...
Page 46: ...46 WSAN XSC3 MF 90 4 240 4 M02M40N15 01 8 18 Exchanger replacement ...
Page 47: ...M02M40N15 01 WSAN XSC3 MF 90 4 240 4 47 9 Accessories 9 1 Anti vibration mount support ...