42
WSAN-XSC3 MF 90.4-240.4
M02M40N15-01
8.3 Unit
booklet
It’s advisable to create a unit booklet to take notes of the unit interventions.
In this way it will be easier to adequately note the various interventions and aid any troubleshooting.
Report on the booklet:
•
date
•
intervention description
•
carried out measures etc.
8.4 Standby
mode
If a long period of inactivity is foreseen:
•
turn off the power
•
avoid the risk of frost (empty the system or add glycol)
Turn off the power to avoid electrical risks or damages by lightning strikes.
With lower temperatures keep heaters turned on in of the electrical panel (option).
It’s recommended that the re-start after the stopping period is performed by a qualified technician, especially after seasonal stops or seasonal
switching.
When restarting, refer to what is indicated in the “start-up” section.
Schedule technical assistance in advance to avoid hitches and to guarantee that the system can be used when required.
8.5 Air
coil
Contact with the exchanger fins can cause cuts: wear protective gloves to perform the above described operations.
It is extremely important that the battery gives the maximum thermal exchange; therefore, its surface must be cleaned from dust and deposits.
Remove all impurities from the surface.
Using an air pressure gun, clean the aluminum surface of the battery; be careful to direct the air in the opposite direction of the fan air
movement.
Hold the gun parallel to the fins to avoid damages.
As an alternative, vacumn cleaner can be used to suck impurities from the air input side.
Verify that the aluminum fins are not bent or damaged, in the event of damages contact the authorized assistance center and get the fins
straightened in order to restore the initial condition for an optimal air flow.
8.6 Electric
fans
Check:
•
the fans and the relative protection gridsare well fixed
•
the fan bearings (evident by noise and anomalous vibrations)
•
the terminal protection covers are closed and the cable holders are properly positioned
8.7 Water side exchanger
It is very important for the exchanger to be able to provide the maximum thermal exchange, therefore it is essential for the inner surfaces to
be clean of dirt and incrustations.
Periodically check the difference between the temperature of the supply water and the condensation temperature: if the difference is greater
than 8°C–10°C it is advisable to clean the exchanger.
The clearing must be effected:
•
with circulation opposite to the usual one
•
with a speed at least 1,5 times higher than the nominal one
•
with an appropriate product moderately acid (95% water + 5% phosphoric acid)
•
after the cleaning rinse with water to inhibit the action of any residual product
Summary of Contents for WSAN-XSC3 MF 200.4
Page 20: ...20 WSAN XSC3 MF 90 4 240 4 M02M40N15 01 6 4 Configuration for 2 pipe system ...
Page 45: ...M02M40N15 01 WSAN XSC3 MF 90 4 240 4 45 8 17 Compressor replacement ...
Page 46: ...46 WSAN XSC3 MF 90 4 240 4 M02M40N15 01 8 18 Exchanger replacement ...
Page 47: ...M02M40N15 01 WSAN XSC3 MF 90 4 240 4 47 9 Accessories 9 1 Anti vibration mount support ...