An alarm list is associated with the inputs of each electronic module of the unit.
According to the unit configuration, and then with electronic modules and options, some lists and/or ALARMS can not be
used.
ALARM STRUCTURE
CENTRAL
Unit_1
Mod_comp1
Mod_comp2
Mod_comp3
Mod_Evap
Unit_2
Mod_comp1
Mod_comp2
Mod_comp3
Mod_Evap
PUPMS – PMP
RECOVERY – REC1
example
CEN
: central module alarm
14
: alarm identificative string
E014 : alarm description
CENTRAL MODULE
Str
Name
1
E001 H2O IN temp. probe fault on control module
2
E002 H2O OUT temp. probe fault on control module
3
E003 Outside air temp. probe fault
4
E004 Water Reset input fault
5
E005 Outside RH% probe fault
6
E006 Thermal cut-out alarm pump 1 on control module
7
E007 Thermal cut-out alarm pump 2 on control module
8
E008 Flow switch alarm on control module
9
E009 System pressure alarm
10
E010 Phase monitor alarm
11
E011 Antifreeze alarm on control module
12
E012 Antifreeze pre-alarm on control module
13
E013 Change CENTRAL pump
14
E014 Unit configuration alarm
15
E015 Demand Limit input fault
16
E016 Can net disconnectedness on control module