Chapter 6 - Parameter description [FU1]
6-18
the motor has overheated. It trips in one minute when
150% of rated motor current established in FU2-33 flows
for one minute.
☞
Note:
The set value is the percentage of FU2-33 [Rated
Motor Current].
This is the current at which the motor can run continuously.
Generally, this value is set to ‘100%’ and which means the
rated motor current set in FU2-33. This value must be set
less than FU1-52 [ETH 1min].
☞
Note:
The set value is the percentage of FU2-33 [Rated
Motor Current].
[Motor i
2
t Characteristic Curve]
To make the ETH function (Motor i
2
t) work correctly, the
motor cooling method must be selected correctly according
to the motor.
[Self-cool] is a motor that has a cooling fan connected
directly to the shaft of the motor. Cooling effects of a self-
cooled motor decrease when a motor is running at low
speeds. The motor current is derated as the motor speed
decreases.
[Forced-cool] is a motor that uses a separate motor to
power a cooling fan. As the motor speed changes, the
cooling effects doe not change.
[Load Current Derating Curve]
☞
Note:
Despite the motor current changing frequently due to
load fluctuation or acceleration and deceleration, the
inverter calculates the i
2
t
and accumulates the value to
protect the motor.
FU1-54: Overload Warning Level
FU1-55: Overload Warning Time
The inverter generates an alarm signal when the output
current has reached the FU1-54 [Overload Warning Level]
for the FU1-55 [Overload Warning Time]. The alarm signal
persists for the FU1-55 even if the current has become the
level below the FU1-54.
Multi-function output terminal (AXA-AXC) is used as the
alarm signal output. To output the alarm signal, set I/O 44
[Multifunction Auxiliary Contact Output] to ‘OL’.
☞
Note:
Inverter is not tripped by this function.
☞
Note:
The set value is the percentage of FU2-33 [Rated
FU1
►
ETH cont
52 100 %
100
52
Factory Default:
100 %
100
Load Current [%]
Trip Time
FU1-51
[ETH 1min]
1 minute
FU1-52
[ETH cont]
FU1
►
Motor type
53 Self-cool
0
53
Factory Default:
Self-cool
0
100%
95%
65%
Output Current
20Hz
60Hz
Self-Cool
Forced-Cool
Related Functions:
FU2-33 [Rated Motor Current]
FU1
►
OL level
54 150 %
150
54
Factory Default:
150 %
150
FU1
►
OL time
55 10.0 sec
10.0
55
Factory Default:
10.0 sec
10.0
Summary of Contents for 30 HP30
Page 6: ......
Page 12: ......
Page 16: ...Chapter 1 Installation 1 4 BLANK ...
Page 18: ...Chapter 1 Installation 1 6 BLANK ...
Page 28: ...Chapter 1 Installation 1 16 Notes ...
Page 39: ...Chapter 2 Operation 2 11 Notes ...
Page 40: ......
Page 46: ......
Page 60: ...Chapter 4 Operation Examples 4 14 Notes ...
Page 83: ...Chapter 5 Parameter List 5 23 Notes ...
Page 84: ......
Page 92: ...Chapter 6 Parameter Description DRV 6 8 Notes ...
Page 105: ......
Page 106: ...Chapter 6 Parameter description FU1 6 14 Notes ...
Page 126: ...Chapter 6 Parameter Description FU2 6 34 Notes ...
Page 144: ...Chapter 6 Parameter Description I O 6 52 Notes ...
Page 162: ......
Page 188: ...Chapter 7 Options 7 26 Type 1 Max 400 Watt Type 2 Max 600 Watt A ...
Page 189: ...Chapter 7 Options 7 27 Type 3 ...
Page 194: ......
Page 204: ......
Page 210: ......