Chapter 6 - Parameter description [I/O]
6-35
6.4 Input/Output Group [I/O]
I/O-00: Jump to Desired Code #
Jumping directly to any parameter code can be
accomplished by entering the desired code number. This
code is available only with LCD keypad.
I/O-01 ~ I/O-05: Analog Voltage Input (V1) Signal
Adjustment
This is used to adjust the analog voltage input signal when
the frequency is referenced by the control terminal ‘V1’.
This function is applied when DRV-04 is set to ‘V1’ or
‘V1+I’. Reference frequency versus Analog voltage input
curve can be made by four parameters of I/O-02 ~ I/O-04.
This is the filtering time constant for V1 signal input.
Increase this value if the V1 signal is affected by noise
causing unstable operation of the inverter. Increasing this
value makes response time slower.
This is the minimum voltage of the V1 input at which
inverter outputs minimum frequency.
This is the inverter output minimum frequency when there
is the minimum voltage (I/O-02) on the V1 terminal.
This is the maximum voltage of the V1 input at which
inverter outputs maximum frequency.
This is the inverter output maximum frequency when there
is the maximum voltage (I/O-03) on the V1 terminal.
[Reference Frequency vs. Analog Voltage Input, V1 (0 to 10V)]
I/O-06 ~ I/O-10: Analog Current Input (I) Signal
Adjustment
This is used to adjust the analog current input signal when
the terminal ‘I’ references the frequency. This function is
applied when DRV-04 is set to ‘V1’ or V1+I’. Reference
frequency versus Analog current input curve can be made
by four parameters of I/O-07 ~ I/O-10.
I/O
►
Jump code
00 1
Factory Default:
1
I/O
►
V1 filter
01 10 ms
10
01
Factory Default:
10 ms
10
I/O
►
V1 volt x1
02 0.00 V
0.00
02
Factory Default:
0.00 V
0.00
I/O
►
V1 volt y1
03 0.00 Hz
0.00
03
Factory Default:
0.00 Hz
0.00
I/O
►
V1 volt x2
04 0.00 V
10.00
04
Factory Default:
10.00 V
10.00
I/O
►
V1 volt y2
05 60.00 Hz
60.00
05
Factory Default:
60.00 Hz
60.00
Reference Frequency
I/O-05
Analog Voltage
Input (V1)
I/O-03
I/O-02 I/O-04
Related Functions:
DRV-04 [Frequency Mode]
FU1-20 [Maximum Frequency]
I/O
►
I filter
06 10 ms
10
06
Factory Default:
10 ms
10
Summary of Contents for 30 HP30
Page 6: ......
Page 12: ......
Page 16: ...Chapter 1 Installation 1 4 BLANK ...
Page 18: ...Chapter 1 Installation 1 6 BLANK ...
Page 28: ...Chapter 1 Installation 1 16 Notes ...
Page 39: ...Chapter 2 Operation 2 11 Notes ...
Page 40: ......
Page 46: ......
Page 60: ...Chapter 4 Operation Examples 4 14 Notes ...
Page 83: ...Chapter 5 Parameter List 5 23 Notes ...
Page 84: ......
Page 92: ...Chapter 6 Parameter Description DRV 6 8 Notes ...
Page 105: ......
Page 106: ...Chapter 6 Parameter description FU1 6 14 Notes ...
Page 126: ...Chapter 6 Parameter Description FU2 6 34 Notes ...
Page 144: ...Chapter 6 Parameter Description I O 6 52 Notes ...
Page 162: ......
Page 188: ...Chapter 7 Options 7 26 Type 1 Max 400 Watt Type 2 Max 600 Watt A ...
Page 189: ...Chapter 7 Options 7 27 Type 3 ...
Page 194: ......
Page 204: ......
Page 210: ......